AurFort
ComPact NSXSchneider Electric circuit breaker Compact NSX630F, 36 kA at 415 VAC, Micrologic 1.3 M trip unit 500 A, 3 poles 3d, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

MOLDED CASE CIRCUIT BREAKER

circuit breaker Compact NSX630F, 36 kA at 415 VAC, Micrologic 1.3 M trip unit 500 A, 3 poles 3d

SKU LV432948

A fixed, three-pole ComPact NSX630F motor circuit breaker with a 500 A MicroLogic 1.3 M electronic trip unit. This reference provides instantaneous short-circuit protection and has front connections. Its Icu is 36 kA at 380–415 V AC under IEC 60947-2.

500 ARated current
3PPoles
36 kAIcu at 380–415 V AC
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

LV432948 — selected manufacturer specifications
Product referenceLV432948
RangeComPact
Product nameComPact NSX
Range of productComPact NSX400...630
Device short nameNSX630F
Product or component typeCircuit breaker
Device applicationMotor
Number of poles3P
Protected poles description3t
[In] rated current500 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelF 36 kA 415 V AC
Trip unit nameMicroLogic 1.3 M
Trip unit technologyElectronic
Trip unit protection functionsI
Control typeToggle
Circuit breaker mounting modeFixed
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability2000 cycles at 690 V In 6000 cycles at 690 V In/2 4000 cycles at 440 V In 8000 cycles at 440 V In/2
Mounting supportBackplate
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeI : for short-circuit protection (magnetic)
Trip unit rating500 A at 65 °C
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range6500 A 6000 A 4500 A 5500 A 3500 A 2500 A 3000 A 4000 A 5000 A
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range6500 A
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Number of slots for electrical auxiliaries6 slot(s)
Local signallingFlashing LED (green) for ready to operate
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net weight6.2 kg
StandardsEN/IEC 60947
Product certificationsCCC EAC Marine
Overvoltage categoryClass II
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.