Schneider Electric catalog image for this SKU; may represent the product family.
VAF PF METER
EASYLOGIC DM6200H VAF PF DPM NONC CL1.0
SKU METSEDM6000HCL10NCSchneider Electric METSEDM6000HCL10NC is a vaf pf meter in the EasyLogic DM6X00H NC range. Key specifications include device short name: DM6000H; supply voltage: 48...277 V AC 45...65 Hz; communication port protocol: -.
DM6000HDevice short name
48...277 V AC 45...65 HzSupply voltage
-Communication port protocol
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 17, 2026.
| Product reference | METSEDM6000HCL10NC |
|---|---|
| Range | EasyLogic |
| Product name | EasyLogic DM6X00H NC |
| Device short name | DM6000H |
| Product or component type | VAF PF meter |
| Device application | Remote monitoring |
| Type of measurement | Current Voltage Frequency RPM |
| Metering type | Unbalance current Calculated neutral current Unbalance voltage Rotation speed Phase currents Voltage U21, U32, U13, V1, V2, V3 Frequency Average voltage Vavg Average current Iavg |
| Counter functions | Power interruption ON hour counting |
| [Us] rated supply voltage | 48...277 V AC 45...65 Hz 48...277 V DC |
| Network frequency | 50 Hz 60 Hz |
| [In] rated current | 1 A 5 A |
| type of network | 2P + N 2P 3P + N 3P 1P + N |
| Maximum power consumption in VA | 4 VA at 240 V between phase and neutral |
| Maximum power consumption in W | 2 W at 240 V |
| Display type | 8 segments LED |
| Display colour | Red |
| Messages display capacity | 3 fields of 4 characters |
| Display digits | 12 digit(s) - 14.2 mm in height |
| Communication of data | Reading of measurements Instantaneous and demand values Revolution speed All counters |
| Tamperproof of settings | Protected by access code |
| Sampling rate | 32 samples/cycle |
| Measurement current | 5…6000 mA |
| Signal | Current 0.005...10 A (impedance 0.3 MOhm)6 x |
| Measurement voltage | 35…480 V AC 50...60 Hz between phases 46…277 V AC 50...60 Hz between phase and neutral 277…999000 V AC 50...60 Hz with external VT |
| Frequency measurement range | 45…65 Hz |
| Measurement accuracy | Frequency +/- 0.05 % Power factor +/- 0.01 Current +/- 1 % Voltage +/- 1 % |
| Accuracy class | Class 1 |
| Demand intervals | 1 s |
| Local signalling | Green LED: activity Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) |
| Communication port protocol | - |
| Material | Polycarbonate |
| Flame retardance | V-0 conforming to UL 94 |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Installation category | III |
| Type of installation | Indoor installation |
| Measurement category | Category III 480 V |
| Electrical insulation class | Class II |
| Connections - terminals | Current circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s) Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) |
| Tightening torque | Current circuit: 0.9…1 N.m Philips No 2 screwdriver Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver Control circuit: 0.9…1 N.m Philips No 2 screwdriver |
| Wire stripping length | Current circuit: 3.68 mm Voltage circuit: 7 mm Control circuit: 7 mm |
| Standards | IEC 61010-1:ed. 3 UL 61010-1:ed. 3 |
| Product certifications | CE conforming to IEC 61010-1 CULus conforming to UL 61010-1 CULus conforming to CSA C22.2 No 61010-1 C-Tick |
| Width | 96 mm |
| Depth | Outside : 13 mm Panel : 49 mm |
| Height | 96 mm |
| Net weight | 300 g |
| Electromagnetic compatibility | Electrostatic discharge conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 Surge immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Magnetic field at power frequency conforming to IEC 61000-4-8 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Emission tests conforming to FCC part 15 class A Emission tests conforming to FCC part 15 Subpart C Emission tests conforming to FCC part 15 Subpart E |
| Overvoltage category | III |
| IP degree of protection | IP51 front: conforming to IEC 60529 IP30 body: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C |
| Pollution degree | 2 |
| Ambient air temperature for operation | -10…60 °C |
| Ambient air temperature for storage | -20…70 °C |
| Operating altitude | <= 2000 m |
| service life | 7 year(s) |