AurFort
EasyLogic PM2100Schneider Electric EasyLogic PM2130, Power & Energy meter, up to 31stH, LED, RS485, class 0.5S, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

POWER METER

EasyLogic PM2130, Power & Energy meter, up to 31stH, LED, RS485, class 0.5S

SKU METSEPM2130

Schneider Electric METSEPM2130 is a power meter in the EasyLogic PM2100 range. Key specifications include device short name: PM2130; supply voltage: 80...277 V AC 45...65 Hz +/- 10 %; rated current: 1 A.

PM2130Device short name
80...277 V AC 45...65 Hz +/- 10 %Supply voltage
1 ARated current
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

METSEPM2130 — selected manufacturer specifications
Product referenceMETSEPM2130
RangeEasyLogic
Product nameEasyLogic PM2100
Product or component typePower meter
Device short namePM2130
Device applicationSub billing Power monitoring
Power quality analysistotal harmonic distortion up to the 31st harmonic
Type of measurementApparent power min/max, total Active and reactive power min/max, total Current min/max, avg Voltage min/max, avg Frequency min/max, avg Total current harmonic distortion THD (I) per phase Total voltage harmonic distortion THD (U) per phase Power factor min/max, avg Apparent energy total Active and reactive energy total
Metering typePeak demand currents Active power P, P1, P2, P3 Demand power P, Q, S Reactive power Q, Q1, Q2, Q3 Apparent power S, S1, S2, S3 Active, reactive, apparent energy (signed, four quadrant) Voltage U, U21, U32, U13, V, V1, V2, V3 Current I, I1, I2, I3 Calculated neutral current Unbalance current Peak demand power PM, QM, SM
Accuracy classClass 1 reactive energy conforming to IEC 62053-24 Class 0.5S active energy conforming to IEC 62053-22 Class 5 harmonic distortion (I THD & U THD)
Measurement accuracyApparent power +/- 0.5 % Active energy +/- 0.5 % Reactive energy +/- 1 % Active power +/- 0.5 % Voltage +/- 0.5 % Power factor +/- 0.01 Current +/- 0.5 % Frequency +/- 0.05 %
Measurement current5…6000 mA
Measurement voltage35…480 V AC 50/60 Hz between phases 20…277 V AC 50/60 Hz between phase and neutral 480…999000 V AC 50/60 Hz with external VT
Frequency measurement range45…65 Hz
[Us] rated supply voltage80...277 V AC 45...65 Hz +/- 10 % 100...277 V DC +/- 10 %
Network frequency50 Hz 60 Hz
Ride-through time50 ms 120 V AC typical 50 ms 230 V AC typical 50 ms 125 V DC typical
[In] rated current1 A 5 A
Maximum power consumption in VA8 VA at 277 V AC
Maximum power consumption in W3.3 W (power lines (AC)) 3.3 W at 277 V (power lines (DC))
input impedanceCurrent (impedance <= 0.3 mOhm) Voltage (impedance > 5 MOhm)
Tamperproof of settingsProtected by access code
Display type7 segments LED
Display colourRed
Messages display capacity3 fields of 4 characters
Display digits12 digit(s) - 14.2 mm in height
Demand intervalsConfigurable from 1 to 60 min
Information displayedDemand current (past value) Demand current (present value) Demand power (past value) Demand power (present value) Voltage Current Frequency Energy consumption Harmonic distortion Power factor Active power Apparent power Reactive power Unbalanced in %
Control type3 x button
Local signallingRed LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) Green LED: module operation and integrated communication
Number of inputs0
Number of outputs0
Communication port protocolModbus RTU at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
Communication port supportScrew terminal block: RS485
Data recordingPower logs Time stamping Energy consumption logs Min/max for 8 parameters
Function availableReal time clock
Sampling rate64 samples/cycle
CybersecurityEnable/disable communication ports
Communication serviceRemote monitoring
Product certificationsCE conforming to IEC 61010-1 CULus conforming to UL 61010-1 CULus conforming to CSA C22.2 No 61010-1 RCM EAC C-Tick
Mounting modeClip-on
Mounting positionVertical
Mounting supportFramework
Provided equipment1 x installation guide
Measurement categoryCategory III 480 V Category II 480…600 V
Electrical insulation classClass II Double insulation
Flame retardanceV-0 conforming to UL 94
Connections - terminalsCurrent transformer: screw connection (bottom) 6 Voltage inputs: screw connection (top) 4
MaterialPolycarbonate
Width96 mm
DepthTotal : 76.09 mm Embedded : 61.64 mm
Height96 mm
Net weight300 g
Compatibility codePM2130
service life7 year(s)
IP degree of protectionIP54 front: conforming to IEC 60529 IP30 body: conforming to IEC 60529
Relative humidity5…95 % at 50 °C
Pollution degree2
Ambient air temperature for operation-10…60 °C
Ambient air temperature for storage-25…70 °C
Operating altitude<= 2000 m
Electromagnetic compatibilityElectrostatic discharge conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 Surge immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Magnetic field at power frequency conforming to IEC 61000-4-8 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Emission tests conforming to FCC part 15 class A
Overvoltage categoryIII

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.