AurFort
MVS32HSchneider Electric MVS32H circuit breaker, 3200 A at 40 °C, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CIRCUIT BREAKER

MVS32H circuit breaker, 3200 A at 40 °C

SKU MVS32H3MF5L

Schneider Electric MVS32H3MF5L is a circuit breaker in the MVS32H range. Key specifications include rated current: 3200 A at 40 °C; poles: 3P; trip unit: ET5S.

3200 A at 40 °CRated current
3PPoles
ET5STrip unit
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

MVS32H3MF5L — selected manufacturer specifications
Product referenceMVS32H3MF5L
RangeEasyPact
Product nameMVS32H
Device short nameMVS32H
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3P 3d
[In] rated current3200 A at 40 °C
Network typeAC
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory B
Trip unit nameET5S
Trip unit technologyElectronic
Trip unit rating3200 A
Network frequency50/60 Hz
Control typeManually operated
Mounting modeFixed
Mounting supportBase plate Rail
Connection positionHorizontal Vertical
Location of connectionRear
[Ui] rated insulation voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage12 kV conforming to IEC 60947-2
Circuit breaker CT rating3200 A
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durabilityCategory B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch115 mm without spreader
Contact position indicatorYes
[Icm] rated short-circuit making capacity143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functionsLSI
Protection typeOverload protection (long time) Short time short-circuit protection Instantaneous short-circuit protection
Fault indicationOverload Internal fault Short-circuit
Long time pick-up adjustment type IrAdjustable 9 settings
Long time pick-up adjustment range0.4...1 x In
Long time delay adjustment typeAdjustable 9 settings
[tr] long-time delay adjustment range0.5…24 s at 6 x Ir
Short-time pick-up adjustment type IsdAdjustable 9 settings
[Isd] short-time pick-up adjustment range1.5...10 x Ir
Short-time delay adjustment typeAdjustable 5 settings
[tsd] short-time delay adjustment range100…400 ms
Instantaneous pick-up adjustment type IiAdjustable 9 settings
Instantaneous pick-up adjustment range2...15 x In Off
Zone selective interlocking ZSIWith
Current sensor rating range1000/4000 A
Maximum breaking time25 ms
Maximum closing response time70 ms
Height352 mm
Width422 mm
Depth297 mm
Net weight60 kg
StandardsIEC 60947-2
Product certificationsIEC CCS CCC GOST
Pollution degree4 conforming to IEC 60664-1
IP degree of protectionIP40
Ambient air temperature for operation-5…70 °C
Ambient air temperature for storage-40…85 °C without control unit -25…85 °C with control unit

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.