Schneider Electric catalog image for this SKU; may represent the product family.
ENCLOSURE
Pragma surface enclosure - IP30 - 4 x 13 modules - without door
SKU PRA20413Schneider Electric PRA20413 is a enclosure in the Pragma range. Key specifications include rated current: 90 A; ip protection: IP30 without door; product range: Pragma.
90 ARated current
IP30 without doorIP protection
PragmaProduct range
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 18, 2026.
| Product reference | PRA20413 |
|---|---|
| Range | Pragma |
| Product or component type | Enclosure |
| enclosure type | Distribution enclosure |
| Width | Outside: 336 mm |
| Height | 750 mm |
| Depth | 123 mm |
| Nb of 18 mm modules per row | 13 |
| Nb of horizontal rows | 4 |
| Electrical insulation class | Class II Double insulation |
| Provided equipment | 2 x terminal block 1 x identification label 1 x marking kit 1 x blanking plate strip |
| Type of door | Without |
| Enclosure mounting | Surface |
| 9 mm pitches | 26 |
| Total number of 18 mm modules | 52 |
| Power dissipation in W | 53 W |
| [In] rated current | 90 A |
| [Ui] rated insulation voltage | 400 V |
| Type of rail | DIN |
| Mounting plate description | Without mounting plate |
| cable entry | Cut-out plates Cable or tube Removable plates Trunking |
| Number of terminal blocks | 1 earth (Quick) with 29 outgoers 1 neutral (Quick) with 29 outgoers |
| Distribution block outgoers | 4 x 25 mm² for earth 25 x 4 mm² for earth 4 x 25 mm² for neutral 25 x 4 mm² for neutral |
| Enclosure material | Back part: technoplastic Front face: technoplastic |
| Colour | Enclosure: white (RAL 9016) Front face: grey (RAL 7004) |
| Targeted country | Finland Hungary Czech republic Baltic Sweden Greece Russia |
| Embedding depth | 0 mm |
| Internal depth | 95 mm |
| Fire resistance | Back part: 650 °C Front face: 650 °C |
| IP degree of protection | IP30 without door IP40 with door |
| IK degree of protection | IK08 without door IK09 with door |
| Overvoltage category | II |
| Ambient air temperature for operation | -25…60 °C |
| Standards | IEC 60670-1 IEC 60670-24 IEC 61439-1 IEC 61439-3 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.