Schneider Electric catalog image for this SKU; may represent the product family.
ADDITIONAL NEUTRAL BLOCK
TeSys VARIO - additional neutral block - 175 A - for V5 / V6
SKU VZ13Schneider Electric VZ13 is a additional neutral block in the TeSys range. Key specifications include poles: 1N; operational voltage: 690 V AC 50/60 Hz; ip protection: IP20 conforming to IEC 60529.
1NPoles
690 V AC 50/60 HzOperational voltage
IP20 conforming to IEC 60529IP protection
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 06, 2026.
| Product reference | VZ13 |
|---|---|
| Range | TeSys |
| Device short name | VZ |
| Product or component type | Additional neutral block |
| Performance level | High performance |
| Poles description | 1N |
| Contacts type and composition | 1 NO |
| Contact operation | Early make, late break |
| Product compatibility | V5 V6 |
| Range compatibility | TeSys TeSys VARIO switch disconnector |
| Network type | AC DC |
| Network frequency | 50/60 Hz |
| Mounting location | Left Right |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ith] conventional free air thermal current | 175 A |
| Mechanical durability | 30000 cycles |
| Electrical durability | 30000 cycles DC-1...5 30000 cycles AC-21 |
| Connections - terminals | Screw clamp terminals70 mm² - flexible - with cable end Screw clamp terminals95 mm² - solid |
| Tightening torque | 22.6 N.m - on screw clamp terminals |
| Height | 125 mm |
| Width | 30 mm |
| Depth | 63 mm |
| Net weight | 0.25 kg |
| Standards | IEC 60947-3 |
| Product certifications | UL CSA GL UKCA |
| Protective treatment | TC |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Mechanical robustness | Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6 Shocks 11 ms (15 gn) conforming to IEC 60068-2-27 |
| Ambient air temperature for operation | -20…50 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-1 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.