AurFort
TeSysSchneider Electric Additional pole,TeSys Control,63A,for V3, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

ADDITIONAL POLE

Additional pole,TeSys Control,63A,for V3

SKU VZ3

Schneider Electric VZ3 is a additional pole in the TeSys range. Key specifications include poles: 1P; operational voltage: 690 V AC 50/60 Hz; ip protection: IP20 conforming to IEC 60529.

1PPoles
690 V AC 50/60 HzOperational voltage
IP20 conforming to IEC 60529IP protection
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

VZ3 — selected manufacturer specifications
Product referenceVZ3
RangeTeSys
Device short nameVZ
Product or component typeAdditional pole
Performance levelHigh performance
Poles description1P
Contacts type and composition1 NO
Product compatibilityV3
Range compatibilityTeSys TeSys VARIO switch disconnector
Network typeAC DC
Network frequency50/60 Hz
Suitability for isolationYes
Mounting locationLeft Right
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ith] conventional free air thermal current63 A
[Ithe] conventional enclosed thermal current50 A
Mechanical durability30000 cycles
Electrical durability100000 cycles AC-21 30000 cycles DC-1...5
Connections - terminalsPower circuit: screw clamp terminals16 mm² - flexible - with cable end Power circuit: screw clamp terminals25 mm² - solid
Tightening torquePower circuit: 4 N.m - on screw clamp terminals
Height83 mm
Width20 mm
Depth46 mm
Net weight0.1 kg
StandardsIEC 60947-3
Product certificationsCSA GL UL UKCA
Protective treatmentTC
IP degree of protectionIP20 conforming to IEC 60529
Mechanical robustnessVibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6 Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Ambient air temperature for operation-20…50 °C
Fire resistance960 °C conforming to IEC 60695-2-1

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.