AurFort
Harmony XB4Schneider Electric Single contact block, Harmony XB4, silver alloy, gold flashed, screw clamp terminal, dusty environment, 1NC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACT BLOCK

Single contact block, Harmony XB4, silver alloy, gold flashed, screw clamp terminal, dusty environment, 1NC

SKU ZBE1026P

Schneider Electric ZBE1026P is a contact block in the Harmony XB4 range. Key specifications include ip protection: IP5X; net weight: 0.012 kg; product range: Harmony XB4.

IP5XIP protection
0.012 kgNet weight
Harmony XB4Product range
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

ZBE1026P — selected manufacturer specifications
Product referenceZBE1026P
Range of productHarmony XB4 Harmony XB5
Product or component typeContact block
Device short nameZBE
Sale per indivisible quantity5
IP degree of protectionIP5X
Contact operationSlow-break
Contact block typeSingle
Contacts usageLow power switching contacts
Connections - terminalsScrew clamp terminals, <= 2 x 1.5 mm² with cable end conforming to IEC 60947-1 Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to IEC 60947-1
Net weight0.012 kg
Contacts type and composition1 NC
Positive openingWith conforming to IEC 60947-5-1 appendix K
Operating travel1.5 mm (NC changing electrical state) 4.3 mm (total travel)
Operating force2 N NC changing electrical state
Mechanical durability10000000 cycles
Tightening torque0.8…1.2 N.m conforming to IEC 60947-1
Shape of screw headCross compatible with pozidriv No 1 screwdriver Slotted compatible with flat Ø 4 mm screwdriver Slotted compatible with flat Ø 5.5 mm screwdriver
Contacts materialGold flashed (Ag/Ni/Au) contacts
Short-circuit protection10 A cartridge fuse type gG conforming to IEC 60947-5-1
[Ith] conventional free air thermal current10 A conforming to IEC 60947-5-1
[Ui] rated insulation voltage600 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
[Ie] rated operational current3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1 6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1 0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1 0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1 0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1 1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
Electrical durability1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Mounting of blockFront mounting
Electrical composition codeC9 (quantity <= 3) M5 (quantity <= 2) M9 (quantity <= 2)
Protective treatmentTH
Ambient air temperature for storage-40…70 °C
Ambient air temperature for operation-40…70 °C
StandardsCSA C22.2 No 14 UL 508 IEC 60947-5-1 IEC 60947-5-4 IEC 60947-1 JIS C8201-5-1 JIS C8201-1
Product certificationsUL LROS (Lloyds register of shipping) CCC CSA GOST BV DNV
Vibration resistance5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
Shock resistance30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27