ABBMS116-10

ABB catalog image for this SKU; may represent the product family.
MOTOR PROTECTION CIRCUIT-BREAKER
MS116-10
SKU 1SAM250000R1010ABB MS116-10: Motor protection circuit-breaker. Pole configuration: 3P.
3PPoles
MS116-10Product range
Motor protection circuit-breakerProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 09, 2026.
| Product ID | 1SAM250000R1010 |
|---|---|
| Catalog Description | MS116-10 Manual Motor Starter 6.3 ... 10 A |
| Country of Origin | India Germany |
| Lead Time | 0 day 999 day 21 day |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active |
| Quote Only | No Yes |
| Stocked At Warehouses | AETAD009EXPU BRABB008EXPU BRAPR001EXPU CHNOR001EXPU CHSEC006EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU CZABB006EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB003EXPU INABB015EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU USSVCEXPU ZATAD021EXPU |
| Configuration Only | No |
| Criticality | No |
| Note | No |
| Product Availability Class | Replaced |
| Replacement Part ID | 64693000 |
| Storage Location | 4001 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362010 |
| Data Sheet, Technical Information | 2CDC131025D0201 |
| Instructions and Manuals | 2CDC131011M6802 |
| Instructions and Manuals (Part 2) | 2CDC131060M0202 |
| Time-Current Characteristic Curve | 1SAM200505F0010 |
| I²t Characteristic | 1SAM200507F0001 1SAM200507F0002 1SAM200507F0003 |
| Cut-off Current Characteristic | 1SAM200508F0001 1SAM200508F0002 1SAM200508F0003 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimension Diagram | 1SAM200422F0001 |
| Product Net Width | 45 mm |
| Product Net Height | 90 mm |
| Product Net Depth / Length | 85.6 mm |
| Product Net Weight | 0.265 kg |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 50 kA (400 V AC) 50 kA (440 V AC) 6 kA (500 V AC) 6 kA (690 V AC) 2 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 75 kA (400 V AC) 75 kA (440 V AC) 18 kA (500 V AC) 15 kA (690 V AC) 3 kA |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 150 A |
| Setting Range | 6.3 ... 10 A |
| Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 4 kW |
| Rated Operational Power AC-3e (Pe) | (400 V) Three Phase 4 kW |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Operational Current (Ie) | 10 A |
| Rated Operational Current AC-3 (Ie) | 10 A |
| Rated Operational Current AC-3e (Ie) | 10 A |
| Rated Frequency (f) | Main Circuit 50 Hz Main Circuit 60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
| Rated Insulation Voltage (Ui) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 0.9 ... 2.4 W |
| Number of Poles | 3P |
| Conventional Free-air Thermal Current (Ith) | Main Circuit 10 A |
| Degree of Protection | Housing IP20 Main Circuit Terminals IP10 |
| Pollution Degree | 3 |
| Electrical Durability | 100000 cycle |
| Mechanical Durability | Nr. Operations 100000 cycle |
| Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm² Flexible 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1 ... 4 mm² |
| Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm |
| Recommended Screw Driver | Pozidriv 2 |
| Mounting Position | 1 ... 6 any |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 400 V 0 mm Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 0 mm Other Device Same Type, Vertical 150 mm |
| Contact Position Indication | ON / OFF |
| Standards | IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L |
| Short-Circuit Current Rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 18 kA Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kA Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 18 kA Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Horsepower Rating UL/CSA | (200 V AC) Three Phase 2 Hp (208 V AC) Three Phase 2 Hp (220 ... 240 V AC) Three Phase 3 Hp (440 ... 480 V AC) Three Phase 5 Hp (550 ... 600 V AC) Three Phase 7.5 Hp |
| Full Load Amps Motor Use | (200 V AC) Three Phase 7.8 A (208 V AC) Three Phase 7.5 A (220 ... 240 V AC) Three Phase 9.6 A (440 ... 480 V AC) Three Phase 7.6 A (550 ... 600 V AC) Three Phase 9 A |
| Locked Rotor Amps | (200 V AC) Three Phase 57.5 A (208 V AC) Three Phase 55 A (220 ... 240 V AC) Three Phase 64 A (440 ... 480 V AC) Three Phase 46 A (550 ... 600 V AC) Three Phase 50.8 A |
| General Use Rating UL/CSA | (600 V AC) 10 A |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-12 AWG Stranded 1/2x 16-12 AWG |
| Tightening Torque UL/CSA | Main Circuit 10 in·lb |
| Ambient Air Temperature | Around the Enclosure 0 ... +40 °C Operation -25 ... +70 °C Operation Compensated -25 ... +55 °C Storage -50 ... +80 °C |
| Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
| Resistance to Vibrations | 2g 5 ... 150 Hz 5g 3 ... 150 Hz |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SAA963005-4502 |
| RoHS Declaration | 1SAA963006-4501 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006539 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| ABB EcoSolutions Profile | 1SFC100125C0353 |
| End Of Life Disassembling Instructions | 1SAC200331H0001 |
| Environmental Product Declaration - EPD | 1SAC200359H0001 1SAC200384H0001 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 88 % |
| A2L Certificate – IEC | 1SAA963000-4601 |
| ABS Certificate | 1SAA963000-0104 |
| BV Certificate | 1SAA963000-0204 |
| CB Certificate | 1SAA963005-2003 1SAA963006-2001 |
| CCC Certificate | 2024010307654705 2024010307656673 |
| CQC Certificate | CQC2011010307506570 CQC2014010307744794 |
| Declaration of Conformity - CCC | 2020980307003705 2020980307003043 |
| Declaration of Conformity - CE | 1SAD101100-3401 |
| Declaration of Conformity - UKCA | 1SAD201100-3401 |
| DNV Certificate | 1SAA963000-0304 |
| DNV GL Certificate | 1SAA963000-0304 |
| EAC Certificate | 1SAA963000-2701 |
| GL Certificate | 1SAA963000-0402 |
| LR Certificate | 1SAA963000-0505 |
| RMRS Certificate | 1SAA918000-0704 |
| UL Certificate | E137861-20001218 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 92 mm |
| Package Level 1 Depth / Length | 95 mm |
| Package Level 1 Height | 50 mm |
| Package Level 1 Gross Weight | 0.28 kg |
| Package Level 1 EAN | 4013614320330 |
| Package Level 2 Units | carton 40 piece |
| Package Level 2 Width | 280 mm |
| Package Level 2 Depth / Length | 395 mm |
| Package Level 2 Height | 210 mm |
| Package Level 2 Gross Weight | 11.586 kg |
| Package Level 2 EAN | 4013614408700 |
| IDEA Granular Category Code (IGCC) | 4731 >> Manual Starters |
| E-Number (Finland) | 3706010 |
| E-Number (Norway) | 4364276 |
| E-Number (Sweden) | 3111948 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.