AurFort
ABBMS132-25ABB MS132-25, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

MOTOR PROTECTION CIRCUIT-BREAKER

MS132-25

SKU 1SAM350000R1014

ABB MS132-25: Motor protection circuit-breaker. Pole configuration: 3P.

3PPoles
MS132-25Product range
Motor protection circuit-breakerProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SAM350000R1014 — selected manufacturer specifications
Product ID1SAM350000R1014
Catalog DescriptionMS132-25 Manual Motor Starter 20 ... 25 A
Configuration OnlyNo
Country of OriginGermany China India
CriticalityNo
Lead Time8 day 0 day 28 day
Made To OrderNo
NoteNo
Product Availability ClassStandard delivery time
Product Sales StatusActive Inactive
Quote OnlyNo
Stocked At WarehousesBRAPR001EXPU CHNOR001EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB015EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU
Storage Location4001
Warranty ReturnProduct under warranty must be returned
Minimum Order Quantity1 piece
Customs Tariff Number85362010
Data Sheet, Technical Information2CDC131021D0202
Instructions and Manuals2CDC131022M6802
Instructions and Manuals (Part 2)2CDC131060M0202
Ex Operating Instructions2CDC131063M6801
Time-Current Characteristic Curve1SAM300505F0014
I²t Characteristic1SAM300507F0001 1SAM300507F0003 1SAM300507F0002
Cut-off Current Characteristic1SAM300508F0001 1SAM300508F0003
CAD Dimensional Drawing2CDC001079B0201
Dimension Diagram1SAM300402F0002
Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.55 mm
Product Net Weight0.31 kg
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 50 kA (250 V DC) 3 Poles in Series 10 kA (400 V AC) 50 kA (440 V AC) 30 kA (500 V AC) 10 kA (690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(230 V AC) 50 kA (400 V AC) 50 kA (440 V AC) 30 kA (500 V AC) 10 kA (690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)375 A
Setting Range20 ... 25 A
Rated Operational Power AC-3 (Pe)(400 V) Three Phase 11 kW
Rated Operational Power AC-3e (Pe)(400 V) Three Phase 11 kW
Rated Operational VoltageMain Circuit 690 V AC Main Circuit 250 V DC
Rated Operational Current (Ie)25 A
Rated Operational Current AC-3 (Ie)25 A
Rated Operational Current AC-3e (Ie)25 A
Rated Operational Current DC-5 (Ie)25 A
Rated Frequency (f)Main Circuit 50 Hz Main Circuit 60 Hz
Operating Frequency (fsw)0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Power Lossat Rated Operating Conditions per Pole 1.8 ... 2.8 W
Number of Poles3P
Conventional Free-air Thermal Current (Ith)Main Circuit 25 A
Degree of ProtectionHousing IP20 Main Circuit Terminals IP10
Pollution Degree3
Electrical Durability50000 cycle
Mechanical DurabilityNr. Operations 100000 cycle
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 6 mm² Flexible 1/2x 1 ... 2.5 mm² Flexible 1/2x 2.5 ... 6 mm² Rigid 1/2x 1 ... 2.5 mm² Rigid 1/2x 2.5 ... 6 mm²
Tightening TorqueMain Circuit 2 N·m
Wire Stripping LengthMain Circuit 10 mm
Recommended Screw DriverPozidriv 2
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Horizontal - Up to 400 V 0 mm Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 0 mm Other Device Same Type, Vertical 150 mm
Contact Position IndicationON / OFF / TRIP
StandardsIEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
RemarksUL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx
Short-Circuit Current Rating (SCCR)Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 30 kA Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 35 kA Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kA Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
Maximum Operating Voltage UL/CSAAuxiliary Circuit 250 V AC/DC Main Circuit 600 V AC
Horsepower Rating UL/CSA(200 V AC) Three Phase 5 Hp (208 V AC) Three Phase 7.5 Hp (220 ... 240 V AC) Three Phase 7.5 Hp (440 ... 480 V AC) Three Phase 15 Hp (550 ... 600 V AC) Three Phase 20 Hp
Full Load Amps Motor Use(200 V AC) Three Phase 17.5 A (208 V AC) Three Phase 24.2 A (220 ... 240 V AC) Three Phase 22 A (440 ... 480 V AC) Three Phase 21 A (550 ... 600 V AC) Three Phase 22 A
Locked Rotor Amps(200 V AC) Three Phase 105.8 A (208 V AC) Three Phase 140 A (220 ... 240 V AC) Three Phase 127 A (440 ... 480 V AC) Three Phase 116 A (550 ... 600 V AC) Three Phase 116 A
General Use Rating UL/CSA(600 V AC) 25 A
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-8 AWG Stranded 1/2x 16-8 AWG
Tightening Torque UL/CSAMain Circuit 18 in·lb
Ambient Air TemperatureAround the Enclosure 0 ... +40 °C Operation -25 ... +70 °C Operation Compensated -25 ... +60 °C Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SAA963005-4502
RoHS Declaration1SAA963006-4501
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006539
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill UL 2799 Zero Waste To Landfill Validation available
ABB EcoSolutions Profile1SFC100125C0353
End Of Life Disassembling Instructions1SAC200332H0001
Environmental Product Declaration - EPD1SAC200360H0001 1SAC200385H0001
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 80 %
A2L Certificate – IEC1SAA963000-4601
ABS Certificate1SAA963001-0101
ATEX Certificate1SAA963000-3902
BV Certificate1SAA963001-0202
CB Certificate1SAA963002-2002 1SAA963007-2002
CCC Certificate2024010307654702 2024010307658958
CQC CertificateCQC2010010307387700 CQC2019010307243864
Declaration of Conformity - CCC2020980307003526 2020980307003041
Declaration of Conformity - CE1SAD101100-3402
Declaration of Conformity - UKCA1SAD201100-3402
DNV GL Certificate1SAA963001-0304
EAC Certificate1SAA963000-2701
IECEx Certificate1SAA963000-4001
LR Certificate1SAA963001-0503
RINA Certificate1SAA963002-0802
RMRS Certificate1SAA918000-0704
UL CertificateE137861-20090225 E345003-20090225
Package Level 1 Unitsbox 1 piece
Package Level 1 Width92 mm
Package Level 1 Depth / Length102 mm
Package Level 1 Height50 mm
Package Level 1 Gross Weight0.325 kg
Package Level 1 EAN4013614400148
Package Level 2 Unitscarton 40 piece
Package Level 2 Width280 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Height210 mm
Package Level 2 Gross Weight13.386 kg
Package Level 2 EAN4013614409042
IDEA Granular Category Code (IGCC)4731 >> Manual Starters
E-Number (Finland)3705998
E-Number (Norway)4364082
E-Number (Sweden)3112129

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.