ELECTRONIC OVERLOAD RELAY

EF65-70

SKU 1SAX331001R1101

ABB EF65-70: Electronic overload relay. Pole configuration: 3P.

3PPoles
EF65-70Product range
Electronic overload relayProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SAX331001R1101 — selected manufacturer specifications
Product ID1SAX331001R1101
Catalog DescriptionEF65-70 Electronic Overload Relay 25 ... 70 A
Country of OriginIndia
Lead Time0 day
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesAETAD009EXPU BRABB008EXPU CHSEC006EXPU INABB003EXPU INABB015EXPU
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Data Sheet, Technical Information2CDC107041D0201
Instructions and Manuals2CDC107026M6803
Instructions and Manuals (Part 2)1SAC200017M0002
Ex Operating Instructions2CDC107043M6801
Time-Current Characteristic Curve1SAX100509F0002 1SAX100510F0001
CAD Dimensional Drawing2CDC001079B0201
Dimension Diagram1SAX300405F0001
Product Net Width70 mm
Product Net Height131.2 mm
Product Net Depth / Length105.2 mm
Product Net Weight0.821 kg
Setting Range25 ... 70 A
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC Main Circuit 1000 V AC
Rated Operational Current (Ie)70 A
Rated Frequency (f)Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Main Circuit 50 Hz Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Auxiliary Circuit 6 kV Main Circuit 8 kV
Rated Insulation Voltage (Ui)1000 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (Ith)Auxiliary Circuit NC 6 A Auxiliary Circuit NO 6 A
Rated Operational Current AC-15 (Ie)(240 V) NC 3 A (240 V) NO 3 A (400 V) NC 1.1 A (400 V) NO 1.1 A (500 V) NC 0.75 A (500 V) NO 0.75 A
Rated Operational Current DC-13 (Ie)(125 V) NC 0.55 A (125 V) NO 0.5 A (24 V) NC 1.5 A (24 V) NO 1.5 A (250 V) NC 0.27 A (250 V) NO 0.27 A (60 V) NC 0.55 A (60 V) NO 0.55 A
Degree of ProtectionHousing IP20 Main Circuit Terminals IP10
Pollution Degree3
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm² Flexible 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1x 4 ... 35 mm² Flexible with Ferrule 2x 2.5 ... 35 mm² Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² Flexible 1/2x 4 ... 35 mm² Rigid 1/2x 4 ... 35 mm²
Tightening TorqueAuxiliary Circuit 0.8 ... 1.2 N·m Main Circuit 4 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm Main Circuit 20 mm
Recommended Screw DriverAuxiliary Circuit Pozidriv 2 Main Circuit Pozidriv 2
Mounting Position1 ... 6
Power Lossat Rated Operating Conditions per Pole 0.056 ... 0.441 W
Suitable ForAF40 AF52 AF65
StandardsIEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600 (NC:) Q600 (NO:) B600 (NO:) Q600
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 10-2 AWG Stranded 1/2x 10-2 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-10 AWG Stranded 1/2x 18-10 AWG
Tightening Torque UL/CSAAuxiliary Circuit 7 ... 1 in·lb Main Circuit 55 in·lb
Ambient Air TemperatureOperation -25 ... +70 °C Operation Compensated -25 ... +70 °C Storage -50 ... +85 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
ABB EcoSolutions Profile1SFC100125C0415
End Of Life Disassembling Instructions1SAC200283H0001
Environmental Information1SAC200098H0001
Environmental Product Declaration - EPD1SAC200236H0001
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 90.6 %
ABS Certificate1SAA941002-0102
ATEX Certificate1SAA941004-3901
BV Certificate1SAA941002-0201
CB Certificate1SAA964013-2001
CCC Certificate2024010304636746
CCS Certificate1SAA941001-0901
CQC CertificateCQC2013010309592132
Declaration of Conformity - CCC2020980309000286
Declaration of Conformity - CE1SAD101100-3601
Declaration of Conformity - UKCA1SAD201100-3601
DNV Certificate1SAA941003-0302
EAC Certificate1SAA941003-2701
IECEx Certificate1SAA941000-4001
LR Certificate1SAA941002-0501
RINA CertificateRINA_ELE376813CS
RMRS Certificate1SAA941001-0701
UL CertificateE48139-19990512
Package Level 1 Unitsbox 1 piece
Package Level 1 Width139 mm
Package Level 1 Height107 mm
Package Level 1 Depth / Length75.5 mm
Package Level 1 Gross Weight0.876 kg
Package Level 1 EAN4013614442254
IDEA Granular Category Code (IGCC)5365 >> Electronic overload relay
E-Number (Finland)3706580
E-Number (Norway)4116700
E-Number (Sweden)3210245

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.