ABBT16-1.7

ABB catalog image for this SKU; may represent the product family.
THERMAL OVERLOAD RELAY
T16-1.7
SKU 1SAZ711201R1028ABB T16-1.7: Thermal overload relay. Pole configuration: 3P.
3PPoles
T16-1.7Product range
Thermal overload relayProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 08, 2026.
| Product ID | 1SAZ711201R1028 |
|---|---|
| Catalog Description | T16-1.7 Thermal Overload Relay 1.3 ... 1.7 A |
| Country of Origin | India |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | INABB015EXPU |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Data Sheet, Technical Information | 2CDC106020D0201 |
| Instructions and Manuals | 2CDC106019M6802 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| Time-Current Characteristic Curve | 1SAZ700505F0010 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimension Diagram | 1SAZ700404F0001 |
| Product Net Width | 45 mm |
| Product Net Height | 76.7 mm |
| Product Net Depth / Length | 53.5 mm |
| Product Net Weight | 0.1 kg |
| Setting Range | 1.3 ... 1.7 A |
| Rated Operational Voltage | Auxiliary Circuit 600 V AC/DC Main Circuit 690 V AC |
| Rated Operational Current (Ie) | 1.7 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Main Circuit 50 Hz Main Circuit 60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV Main Circuit 6 kV |
| Rated Insulation Voltage (Ui) | 690 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC 6 A Auxiliary Circuit NO 4 A |
| Rated Operational Current AC-15 (Ie) | (120 V) NC 3 A (120 V) NO 0.5 A (240 V) NC 3 A (240 V) NO 0.5 A (400 V) NC 0.75 A (400 V) NO 0.5 A (500 V) NC 0.75 A (500 V) NO 0.5 A |
| Rated Operational Current DC-13 (Ie) | (125 V) NC 0.55 A (125 V) NO 0.55 A (24 V) NC 1.25 A (24 V) NO 1.25 A (250 V) NC 0.27 A (250 V) NO 0.27 A (500 V) NC 0.15 A (500 V) NO 0.15 A (60 V) NC 0.55 A (60 V) NO 0.55 A |
| Degree of Protection | IP20 |
| Pollution Degree | 3 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Flexible 1/2x 0.75 ... 1 mm² Flexible 1/2x 1 ... 2.5 mm² Rigid 1/2x 0.75 ... 4 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 4 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm² Flexible 1/2x 0.75 ... 4 mm² Solid 1/2x 0.75 ... 1.5 mm² Solid 1/2x 1.5 ... 4 mm² Stranded 1/2x 1 ... 4 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.2 N·m Main Circuit 1.1 ... 1.5 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm Main Circuit 12 mm |
| Recommended Screw Driver | Main Circuit Pozidriv 2 |
| Power Loss | at Rated Operating Conditions per Pole 1.1 ... 2.0 W |
| Suitable For | B6 BC6 B7 BC7 VB6 VBC6 VB7 VBC7 MC1 MC2 AS09 AS12 AS16 |
| Standards | IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 (NC:) Q600 (NO:) Q600 (NO:) D300 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 18-12 AWG Stranded 1/2x 18-10 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-12 AWG Stranded 1/2x 18-12 AWG |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 ... 11 in·lb Main Circuit 9 ... 13 in·lb |
| Ambient Air Temperature | Operation -25 ... +60 °C Operation Compensated -25 ... +60 °C Storage -50 ... +80 °C |
| Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 22g |
| Resistance to Vibrations | 3g 3 ... 150 Hz |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| Environmental Information | 1SAC200055H0009 |
| A2L Certificate – IEC | 1SAA941000-4601 |
| ABS Certificate | 1SAA941001-0102 |
| BV Certificate | 1SAA941001-0203 |
| CB Certificate | 1SAA941008-2001 |
| CCC Certificate | 2024010304658957 |
| CQC Certificate | CQC2011010309459316 |
| Declaration of Conformity - CCC | 2020980304001787 |
| Declaration of Conformity - CE | 1SAD101100-3502 |
| Declaration of Conformity - UKCA | 1SAD201100-3502 |
| DNV GL Certificate | 1SAA941001-0302 |
| EAC Certificate | 1SAA941002-2702 |
| GL Certificate | 1SAA941007-0401 |
| LR Certificate | 1SAA941001-0502 |
| RINA Certificate | 1SAA941000-0802 |
| RMRS Certificate | 1SAA941000-0704 |
| UL Certificate | E48139-20090126 |
| Package Level 1 Units | carton 1 piece |
| Package Level 1 Width | 48 mm |
| Package Level 1 Height | 63 mm |
| Package Level 1 Depth / Length | 82 mm |
| Package Level 1 Gross Weight | 0.112 kg |
| Package Level 1 EAN | 4013614397899 |
| Package Level 2 Units | 40 piece |
| Package Level 2 Width | 280 mm |
| Package Level 2 Height | 210 mm |
| Package Level 2 Depth / Length | 395 mm |
| Package Level 2 Gross Weight | 8.45 kg |
| Package Level 2 EAN | 4013614440601 |
| IDEA Granular Category Code (IGCC) | 5366 >> Thermal overload relay |
| E-Number (Finland) | 3706142 |
| E-Number (Norway) | 4117159 |
| E-Number (Sweden) | 3212063 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.