AurFort
ABBTF65-47ABB TF65-47, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

THERMAL OVERLOAD RELAY

TF65-47

SKU 1SAZ811201R1004

ABB TF65-47: Thermal overload relay. Pole configuration: 3P.

3PPoles
TF65-47Product range
Thermal overload relayProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SAZ811201R1004 — selected manufacturer specifications
Product ID1SAZ811201R1004
Catalog DescriptionTF65-47 Thermal Overload Relay 36 ... 47 A
Configuration OnlyNo
Country of OriginChina India
CriticalityNo
Lead Time35 day 0 day
Made To OrderNo
NoteNo
Product Availability ClassStandard delivery time
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesBRAPR001EXPU CHNOR001EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB015EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU
Storage Location4001
Warranty ReturnProduct under warranty must be returned
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Data Sheet, Technical Information2CDC106069D0201
Instructions and Manuals2CDC106051M6803
Instructions and Manuals (Part 2)1SAC200017M0002
Ex Operating Instructions2CDC106085M6801
Time-Current Characteristic Curve1SAZ800502F0004
CAD Dimensional Drawing2CDC001079B0201
Dimension Diagram1SAZ800401F0001
Product Net Width54.9 mm
Product Net Height101.4 mm
Product Net Depth / Length106.9 mm
Product Net Weight0.372 kg
Setting Range36 ... 47 A
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC Main Circuit 690 V AC Main Circuit 440 V DC
Rated Operational Current (Ie)47 A
Rated Frequency (f)Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Main Circuit 50 Hz Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Auxiliary Circuit 6 kV Main Circuit 8 kV
Rated Insulation Voltage (Ui)690 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (Ith)Auxiliary Circuit NC 6 A Auxiliary Circuit NO 4 A
Rated Operational Current AC-15 (Ie)(120 V) NC 3 A (120 V) NO 0.5 A (240 V) NC 3 A (240 V) NO 0.5 A (400 V) NC 0.75 A (400 V) NO 0.5 A (500 V) NC 0.75 A (500 V) NO 0.5 A
Rated Operational Current DC-13 (Ie)(125 V) NC 0.55 A (125 V) NO 0.55 A (24 V) NC 1.25 A (24 V) NO 1.25 A (250 V) NC 0.27 A (250 V) NO 0.27 A (500 V) NC 0.15 A (500 V) NO 0.15 A (60 V) NC 0.55 A (60 V) NO 0.55 A
Degree of ProtectionHousing IP20 Main Circuit Terminals IP10
Pollution Degree3
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Flexible 1/2x 0.75 ... 1 mm² Flexible 1/2x 1 ... 2.5 mm² Rigid 1/2x 0.75 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 2.5 ... 10 mm² Flexible with Ferrule 1x 2.5 ... 35 mm² Flexible with Insulated Ferrule 1x 2.5 ... 35 mm² Flexible with Insulated Ferrule 1/2x 2.5 ... 10 mm² Flexible 1/2x 2.5 ... 16 mm² Flexible 1x 2.5 ... 35 mm² Rigid 1/2x 2.5 ... 16 mm² Rigid 1x 2.5 ... 35 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m Main Circuit 4.0 ... 4.5 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm Main Circuit 17 mm
Recommended Screw DriverAuxiliary Circuit Pozidriv 2 Main Circuit Pozidriv 2
Mounting Position1 ... 6
Power Lossat Rated Operating Conditions per Pole 2.1 ... 3.6 W
Suitable ForAF40 AF52 AF65
StandardsIEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600 (NC:) Q600 (NO:) Q600 (NO:) D300
Connecting Capacity Main Circuit UL/CSAFlexible 1x 12-2 AWG Flexible 2x 12-6 AWG Stranded 1x 12-2 AWG Stranded 2x 12-6 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-12 AWG Stranded 1/2x 18-12 AWG
Tightening Torque UL/CSAAuxiliary Circuit 9 ... 11 in·lb Main Circuit 35 ... 40 in·lb
Ambient Air TemperatureOperation -40 ... +70 °C Operation Compensated -40 ... +70 °C Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
ABB EcoSolutions Profile1SFC100125C0355
End Of Life Disassembling Instructions1SAC200334H0001
Environmental Information1SAC200058H0009
Environmental Product Declaration - EPD1SAC200249H0001
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 93.3 %
A2L Certificate – IEC1SAA941000-4601
ABS Certificate1SAA941003-0101
ATEX Certificate1SAA941005-3901
BV Certificate1SAA941001-0203
CB Certificate1SAA941015-2001
CCC Certificate2024010304636179
CQC CertificateCQC2014010309689432
Declaration of Conformity - CCC2020980309000291
Declaration of Conformity - CE1SAD101100-3503
Declaration of Conformity - UKCA1SAD201100-3503
DNV GL Certificate1SAA941004-0301
EAC Certificate1SAA941002-2701
IECEx Certificate1SAA941001-4001
LR Certificate1SAA941003-0501
RINA CertificateRINA_ELE098115XG
RMRS Certificate1SAA941002-0701
UL CertificateE48139-20130329
Package Level 1 Unitsbox 1 piece
Package Level 1 Width123 mm
Package Level 1 Height121 mm
Package Level 1 Depth / Length82 mm
Package Level 1 Gross Weight0.456 kg
Package Level 1 EAN4013614482946
Package Level 2 Units12 piece
Package Level 2 Width280 mm
Package Level 2 Height210 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Gross Weight5.858 kg
Package Level 2 EAN4013614485343
IDEA Granular Category Code (IGCC)5366 >> Thermal overload relay
E-Number (Finland)3706586
E-Number (Norway)4116789
E-Number (Sweden)3210266

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.