ABBAF26-40-00-13

ABB catalog image for this SKU; may represent the product family.
POWER CONTACTOR, AC SWITCHING
AF26-40-00-13
SKU 1SBL237201R1300ABB AF26-40-00-13: Power contactor, AC switching. Pole configuration: 4P.
4PPoles
AF26-40-00-13Product range
Power contactor, AC switchingProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 09, 2026.
| Product ID | 1SBL237201R1300 |
|---|---|
| Catalog Description | AF26-40-00-13 100-250V50/60HZ-DC Contactor |
| Country of Origin | India |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | INABB015EXPU |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| EPLAN Data | 9AAC159659_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 101 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.36 kg |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1 |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 45 A (690 V) 60 °C 40 A (690 V) 70 °C 32 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 21.2 A (440 V) 60 °C 20 A (500 V) 60 °C 17.6 A (690 V) 60 °C 10.5 A (380 / 400 V) 60 °C 22 A (220 / 230 / 240 V) 60 °C 23.2 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 45 A (110 V) 2 Poles in Series, 60 °C 40 A (110 V) 2 Poles in Series, 70 °C 32 A (110 V) 3 Poles in Series, 40 °C 45 A (110 V) 3 Poles in Series, 60 °C 40 A (110 V) 3 Poles in Series, 70 °C 32 A (110 V) 4 Poles in Series, 40 °C 45 A (110 V) 4 Poles in Series, 60 °C 40 A (110 V) 4 Poles in Series, 70 °C 32 A (220 V) 3 Poles in Series, 40 °C 45 A (220 V) 3 Poles in Series, 60 °C 40 A (220 V) 3 Poles in Series, 70 °C 32 A (220 V) 4 Poles in Series, 40 °C 45 A (220 V) 4 Poles in Series, 60 °C 40 A (220 V) 4 Poles in Series, 70 °C 32 A (72 V) 1-Pole, 40 °C 45 A (72 V) 1-Pole, 60 °C 40 A (72 V) 1-Pole, 70 °C 32 A (72 V) 2 Poles in Series, 40 °C 45 A (72 V) 2 Poles in Series, 60 °C 40 A (72 V) 2 Poles in Series, 70 °C 32 A (72 V) 3 Poles in Series, 40 °C 45 A (72 V) 3 Poles in Series, 60 °C 40 A (72 V) 3 Poles in Series, 70 °C 32 A (72 V) 4 Poles in Series, 40 °C 45 A (72 V) 4 Poles in Series, 60 °C 40 A (72 V) 4 Poles in Series, 70 °C 32 A |
| Rated Operational Power AC-3 (Pe) | (400 V) 11 kW (415 V) 11 kW (440 V) 11 kW (500 V) 11 kW (690 V) 9 kW (220 / 230 / 240 V) 5.5 kW |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1.6 W at Rated Operating Conditions AC-3 per Pole 0.42 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms Between Coil De-energization and NO Contact Opening 11 ... 95 ms Between Coil Energization and NC Contact Opening 38 ... 90 ms Between Coil Energization and NO Contact Closing 40 ... 95 ms |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1.5 ... 16 mm² Flexible with Insulated Ferrule 1/2x 1.5 ... 16 mm² Rigid Solid 1/2x 1.5 ... 4 mm² Rigid Stranded 1/2x 1.5 ... 16 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid Solid 1/2x 1 ... 2.5 mm² Rigid Stranded 1/2x 1 ... 2.5 mm² |
| Wire Stripping Length | Control Circuit 10 mm Main Circuit 12 mm |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
| Tightening Torque | Control Circuit 1.2 N·m Main Circuit 2.5 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 45 A |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 16-10 AWG Rigid Stranded 1/2x 16-6 AWG |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG Rigid Stranded 1/2x 18-14 AWG |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb Main Circuit 22 in·lb |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g Open, Shock Direction: B1 5 g Shock Direction: A 30 g Shock Direction: B2 15 g Shock Direction: C1 25 g Shock Direction: C2 25 g |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 894b9a15-6d1a-4a7a-b1e2-f88ca8aeada0 France |
| Simplified SCIP | 064d1765-4346-4250-a872-be33228af641 Finland 0f040ca9-f03f-4c5a-a35e-56f279e5e40d Norway 16229975-8743-4fc2-b5f0-a80871880e66 Portugal 2b573fed-f7a0-4e04-9964-f9b3ddfd660e Denmark 396060ec-c30d-4b79-adeb-d2427e23e2b4 Poland 3d72bd32-64aa-4d40-a793-6705ff620f0f Hungary 3e6acbff-7d1b-4f16-be78-64e8ab78fd89 Greece 3eac4d6d-bfd4-4c41-85b9-4a286f67f48d Croatia 40f8c5ca-cd7f-4793-8da2-6a5f6f6b66a6 France 47811304-6522-494f-8cdc-5f2e1b7e0128 Sweden 4e3023d5-bed9-4693-bc33-9e65dc7fdbe5 Poland 6192283f-cfbc-4d8f-abd0-e9ee0998e207 Bulgaria 63c6371b-248b-4b39-981d-d4c4e1d801ea Spain 648436d1-7bf5-4740-acf1-1fbdad4c6be2 Italy 80cccc34-f18b-439c-b21d-54d92b7d425d Hungary 8e25a9ec-19df-45d7-9e07-5fe3b3323269 Estonia 90c25723-65d6-4a25-a2ae-870681008c3e Germany 91ba99ca-3fd9-4020-8827-4ab346e55de8 Sweden 99a9f902-ab47-452c-8e67-11c88c51c283 Belgium a9a4a28f-2ba7-4da1-a9fd-7d71b9467c6b Germany bf04af50-eab9-47cf-b0b2-14cbaf957ea3 Germany c61f4049-4672-4303-8841-e78946cc1dcc Czechia e20cb3e3-e4e9-4d62-8711-f7f8d7b9989d Germany ec5f1824-097b-4644-8561-74999b600345 Netherlands ec6c5997-4553-4d75-8f8f-27de51cb07f9 Belgium f95629c4-c211-403e-90fb-b0fbb1eb8d6d Poland fa26a288-7e06-4da2-a9c6-5ea2f89a644b Germany |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| ABB EcoSolutions Profile | 1SBC100156C0308 |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E4000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 94.3 % |
| A2L Certificate – UL | 9AKK108469A4875 9AKK108469A4879 |
| ABS Certificate | ABS_26-0348269-PDA_FR |
| BV Certificate | BV_2634H24898C1 |
| CB Certificate | 9AKK108472A2647 |
| CCC Certificate | CCC_2024010304656668 |
| CQC Certificate | CQC2010010304445623 CQC2020010304294316 |
| Declaration of Conformity - CCC | 2020980304001254 2020980304001052 |
| Declaration of Conformity - CE | 1SBD250001U1000 |
| Declaration of Conformity - UKCA | 1SBD250032U1000 |
| DNV Certificate | TAE00001AF-5 |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE142224XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-L319322-13-72119002-5 UL-CA-L319322-43-72119002-6 |
| UL Listing Card | UL_E319322 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 103 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.36 kg |
| Package Level 1 EAN | 3471523115231 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3705830 |
| E-Number (Sweden) | 3211511 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.