ABBAF40-40-00-13

ABB catalog image for this SKU; may represent the product family.
POWER CONTACTOR, AC SWITCHING
AF40-40-00-13
SKU 1SBL347201R1300ABB AF40-40-00-13: Power contactor, AC switching. Pole configuration: 4P.
4PPoles
AF40-40-00-13Product range
Power contactor, AC switchingProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 09, 2026.
| Product ID | 1SBL347201R1300 |
|---|---|
| Catalog Description | AF40-40-00-13 100-250V50/60HZ-DC Contactor |
| Country of Origin | India |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | INABB015EXPU |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| EPLAN Data | 9AAC175972_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101047M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Product Net Width | 70 mm |
| Product Net Depth / Length | 113.5 mm |
| Product Net Height | 125.5 mm |
| Product Net Weight | 1.27 kg |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22 |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 105 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 70 A (690 V) 60 °C 60 A (690 V) 70 °C 50 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 40 A (440 V) 60 °C 40 A (500 V) 60 °C 35 A (690 V) 60 °C 25 A (380 / 400 V) 60 °C 40 A (220 / 230 / 240 V) 60 °C 40 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 22 kW (440 V) 22 kW (500 V) 22 kW (690 V) 22 kW (380 / 400 V) 18.5 kW (220 / 230 / 240 V) 11 kW |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V |
| Coil Consumption | Average Holding Value 50 / 60 Hz 4 V·A Average Holding Value 50 Hz 4 V·A Average Holding Value 60 Hz 4 V·A Average Holding Value DC 2 W Average Holding Value, from Warm State 2 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 3 W at Rated Operating Conditions AC-3 per Pole 1 W |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 4 ... 35 mm² Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² Rigid Stranded 1/2x 6 ... 35 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid Solid 1/2x 1 ... 2.5 mm² Rigid Stranded 1/2x 1 ... 2.5 mm² |
| Wire Stripping Length | Control Circuit 10 mm Main Circuit 16 mm |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Recommended Screw Driver | Pozidriv PZ |
| Tightening Torque | Control Circuit 1.2 N·m Main Circuit 4 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 60 A |
| Connecting Capacity Main Circuit UL/CSA | Rigid Stranded 1/2x 10-2 AWG |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG Rigid Stranded 1/2x 18-14 AWG |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb Main Circuit 35 in·lb |
| Full Load Amps Motor Use | (120 V AC) Single Phase 3 A (200 ... 208 V AC) Three Phase 10 A (220 ... 240 V AC) Three Phase 15 A (240 V AC) Single Phase 7-1/2 A (440 ... 480 V AC) Three Phase 30 A (550 ... 600 V AC) Three Phase 40 A |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Vibrations | 3g Closed Position & 2g Open Position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| ABB EcoSolutions Profile | 1SBC100156C0308 |
| End Of Life Disassembling Instructions | 1SBC101081M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E1000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 91.9 % |
| A2L Certificate – UL | 9AKK108469A4890 9AKK108469A4892 |
| ABS Certificate | ABS_26-0348269-PDA_FR ABS_26-0348269-PDA-DUP_CN |
| BV Certificate | BV_2634H36994C0 |
| CB Certificate | SE-115941 |
| CCC Certificate | CCC_2024010304648524 |
| Declaration of Conformity - CCC | 2020980304001256 |
| Declaration of Conformity - CE | 1SBD250001U1000 |
| Declaration of Conformity - UKCA | 1SBD250032U1000 |
| DNV Certificate | TAE00001AF-5 |
| LR Certificate | LRS_LR23403517TA-02 |
| RMRS Certificate | RMRS_1400682124 |
| UL Certificate | UL-US-L312527-1142-02114102-12 UL-CA-L312527-4142-02114102-12 |
| UL Listing Card | UL_E312527 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 150 mm |
| Package Level 1 Depth / Length | 150 mm |
| Package Level 1 Height | 103 mm |
| Package Level 1 Gross Weight | 1.27 kg |
| Package Level 1 EAN | 3471523133532 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3707257 |
| E-Number (Sweden) | 3210298 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.