POWER CONTACTOR, AC SWITCHING

AF80-40-00-11

SKU 1SBL397201R1100

ABB AF80-40-00-11: Power contactor, AC switching. Pole configuration: 4P.

4PPoles
AF80-40-00-11Product range
Power contactor, AC switchingProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SBL397201R1100 — selected manufacturer specifications
Product ID1SBL397201R1100
Catalog DescriptionAF80-40-00-11 24-60V50/60HZ 20-60VDC Contactor
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
Minimum Order Quantity1 piece
Customs Tariff Number85364900
EPLAN Data9AAC175975_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Instructions and Manuals1SBC101047M6801
Instructions and Manuals (Part 2)1SAC200017M0002
CAD Dimensional Drawing2CDC001079B0201
Product Net Width90 mm
Product Net Depth / Length116 mm
Product Net Height125.5 mm
Product Net Weight1.49 kg
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 125 A (690 V) 60 °C 105 A (690 V) 70 °C 90 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 80 A (440 V) 60 °C 80 A (500 V) 60 °C 65 A (690 V) 60 °C 49 A (1000 V) 60 °C 25 A (380 / 400 V) 60 °C 80 A (220 / 230 / 240 V) 60 °C 80 A
Rated Operational Power AC-3 (Pe)(415 V) 45 kW (440 V) 45 kW (500 V) 45 kW (690 V) 45 kW (1000 V) 35 kW (380 / 400 V) 37 kW (220 / 230 / 240 V) 22 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation 20 ... 60 V
Coil ConsumptionAverage Holding Value 50 / 60 Hz 4 V·A Average Holding Value 50 Hz 4 V·A Average Holding Value 60 Hz 4 V·A Average Holding Value DC 2 W Average Holding Value, from Warm State 2 W
Power Lossat Rated Operating Conditions AC-1 per Pole 8 W at Rated Operating Conditions AC-3 per Pole 3.2 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 or 2 x M6 Screws Placed Diagonally
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 6 ... 50 mm² Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² Rigid Stranded 1x 6 ... 70 mm² Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid Solid 1/2x 1 ... 2.5 mm² Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthControl Circuit 10 mm Main Circuit 17 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Recommended Screw DriverPozidriv PZ
Tightening TorqueControl Circuit 1.2 N·m Main Circuit 6 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 105 A
Connecting Capacity Main Circuit UL/CSARigid Stranded 1/2x 6-1 AWG
Connecting Capacity Control Circuit UL/CSARigid Solid 1/2x 18-14 AWG Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAControl Circuit 11 in·lb Main Circuit 53 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 7-1/2 A (200 ... 208 V AC) Three Phase 25 A (220 ... 240 V AC) Three Phase 30 A (240 V AC) Single Phase 15 A (440 ... 480 V AC) Three Phase 60 A (550 ... 600 V AC) Three Phase 75 A
Ambient Air TemperatureClose to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Vibrations3g Closed Position & 2g Open Position 5 ... 300 Hz
Pollution Degree3
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP68d4c68e-2933-49f3-8d99-9153a7f4eac0 France
Simplified SCIP010293b0-d0c6-4c19-ae49-35290d3fdc27 Czechia 060f08fd-2df5-4db8-99bf-5ead76502dcd Hungary 0ac8f3ae-7dff-4c87-a8b7-72c5d850ff01 Sweden 115e2c98-4fda-4194-9b0f-6e13af7aba3f Romania 19152b87-0138-4c48-9cc2-3acf15cf5f72 Germany 249e4303-db10-474d-bc51-8f2ec53ea623 Netherlands 2763def7-3e5b-4e86-a3bc-19a1212c7a77 Denmark 3387db51-8369-45ac-9cd9-d07a465bb507 Germany 39956474-f1e3-43fe-82eb-65c0b0fa8260 Croatia 41256d37-19e7-43dd-ab77-b28479fbd5df Spain 475c8df0-81ab-4e7d-968f-01ce76235c02 France 5c57483d-0176-4c4e-a1ae-0341f51c318e Belgium 647703b1-52fd-4974-a17c-6e05678f280b Belgium 6a98020b-be8b-443c-8c68-69a85a920b8b Poland 6e699e21-3062-4bc8-98a5-6fc26fa4c09c Sweden 719a3341-a932-4880-a038-5d3c52587ac8 Estonia 7672be41-dea1-4bf5-a76a-2947e7a56e86 Poland 8048198a-8399-492e-9ae4-b8f462654ac2 Greece 9524d187-e354-4105-adb5-05d4c4109547 Norway 960ff7fa-f8ac-4f5f-813e-26a4715f8f3b Poland b7eee56c-e225-4f18-8fb4-09bab452a6d6 Finland c10b3b3f-ee1e-4b47-92a2-d109b2f7586d Italy c4f50c0d-e1ca-4bf4-820e-1415efd770ec Germany c5226ee5-3491-4ea8-aab5-022ea0ba1527 Hungary cd47605f-5f03-4582-acf3-28dca92405dc Germany dc2ef974-978f-463b-83c4-99df2c2b8e15 Germany e0e23321-97ad-4e03-b974-5f75b61db37a Portugal f1404899-9eac-430a-be0b-b89a897dedf8 Bulgaria
Toxic Substances Control Act - TSCA2CMT2023-006525
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
ABB EcoSolutions Profile1SBC100156C0308
End Of Life Disassembling Instructions1SBC101081M6801
Environmental Product Declaration - EPD1SBD250584E2000
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 91.9 %
A2L Certificate – UL9AKK108469A4890 9AKK108469A4892
ABS CertificateABS_26-0348269-PDA_FR ABS_26-0348269-PDA-DUP_CN
BV CertificateBV_2634H36994C0
CB CertificateCB_SE-116522A2
CCC CertificateCCC_2024010304656667
Declaration of Conformity - CCC2020980304001255
Declaration of Conformity - CE1SBD250001U1000
Declaration of Conformity - UKCA1SBD250032U1000
DNV CertificateTAE00001AF-5
LR CertificateLRS_LR23403517TA-02
RMRS CertificateRMRS_1400682124
UL CertificateUL-US-L312527-1142-02114102-12 UL-CA-L312527-4142-02114102-12
UL Listing CardUL_E312527
Package Level 1 Unitsbox 1 piece
Package Level 1 Width150 mm
Package Level 1 Depth / Length150 mm
Package Level 1 Height103 mm
Package Level 1 Gross Weight1.62 kg
Package Level 1 EAN3471523133716
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3707458
E-Number (Sweden)3210313

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.