AurFort
ABBOS630D03PABB OS630D03P, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

FUSE SWITCH DISCONNECTOR

OS630D03P

SKU 1SCA022825R2830

ABB OS630D03P: Fuse switch disconnector. Rated current: Main Circuit 630 A. Pole configuration: 3P.

Main Circuit 630 ARated current
3PPoles
OS630D03PProduct range
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SCA022825R2830 — selected manufacturer specifications
Product ID1SCA022825R2830
Catalog DescriptionOS630D03P SWITCH FUSE
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
Environmental Product Declaration - EPD1SCC311202D0201
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC011021D0201
RoHS Declaration1SCC011020D0201
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA1SCC011025D0201
Data Sheet, Technical Information1SCC311013C0201
Instructions and Manuals1SCC311016M0210
Mechanical DrawingsOS600J03.stp
Degree of Protectionacc. to IEC 60529 IP20
Pollution Degree3
Minimum Order Quantity1 piece
Customs Tariff Number85365080
Country of OriginFinland
Product Net Width343 mm
Product Net Height306 mm
Product Net Depth / Length233 mm
Product Net Weight13.5 kg
Package Level 1 Unitsbox 1 piece
Package Level 1 Width328 mm
Package Level 1 Depth / Length365 mm
Package Level 1 Height260 mm
Package Level 1 Gross Weight13.5 kg
Package Level 1 EAN6417019283432
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 630 A
Conventional Thermal Current (Ithe)Fully Enclosed 570 A
Fuse SizeNH3
Fuse SystemDIN
Handle TypePistol
Mounting TypeBase mounting
Number of Poles3P
Operating ModeFront
Position of Line TerminalsTop In - Bottom Out, Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 46 W Total 138 W
Rated Conditional Short-Circuit Current (Inc)(500 V) 100 kA (690 V) 80 kA
Rated Current (In)Main Circuit 630 A
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Current AC-21A (Ie)(500 V) 630 A (690 V) 630 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 200 kW (400 V) 355 kW (415 V) 355 kW (500 V) 450 kW (690 V) 630 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 18 kiloampere rms
StandardsIEC 60947-3
Switches Operating Mechanism03 (Left Side)
Terminal TypeLug terminals
Terminal Width39 mm
Tightening Torque50 ... 75 N·m
A2L Certificate – IEC1SCC311209D0201
ATEX CertificateNo certification needed
CCC CertificateCCC OS630-800 2016
Declaration of Conformity - CE1SCC311112D2704
DNV GL Certificate1SCC311131D0203
UL CertificateNo certification needed
IDEA Granular Category Code (IGCC)5291 >> Fuse switch disconnector
E-Number (Finland)3661504
E-Number (Sweden)3172091

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.