ABBOS800D03P

ABB catalog image for this SKU; may represent the product family.
FUSE SWITCH DISCONNECTOR
OS800D03P
SKU 1SCA022825R4880ABB OS800D03P: Fuse switch disconnector. Rated current: Main Circuit 800 A. Pole configuration: 3P.
Main Circuit 800 ARated current
3PPoles
OS800D03PProduct range
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 09, 2026.
| Product ID | 1SCA022825R4880 |
|---|---|
| Catalog Description | OS800D03P SWITCH FUSE |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Environmental Product Declaration - EPD | 1SCC311202D0201 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| Data Sheet, Technical Information | 1SCC311013C0201 |
| Instructions and Manuals | 1SCC311016M0210 |
| Mechanical Drawings | OS600J03.stp |
| Degree of Protection | acc. to IEC 60529 IP20 |
| Pollution Degree | 3 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country of Origin | Finland |
| Product Net Width | 343 mm |
| Product Net Height | 306 mm |
| Product Net Depth / Length | 233 mm |
| Product Net Weight | 14.89 kg 32.83 lb |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 328 mm 12.91 in |
| Package Level 1 Depth / Length | 365 mm 14.37 in |
| Package Level 1 Height | 260 mm 10.24 in |
| Package Level 1 Gross Weight | 15.67 kg 34.55 lb |
| Package Level 1 EAN | 6417019283647 |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 800 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 720 A |
| Fuse Size | NH3 |
| Fuse System | DIN |
| Handle Type | Pistol |
| Mounting Type | Base mounting |
| Number of Poles | 3P |
| Operating Mode | Front |
| Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Power Loss | at Rated Operating Conditions per Pole 75 W Total 225 W |
| Rated Conditional Short-Circuit Current (Inc) | (500 V) 100 kA (690 V) 80 kA |
| Rated Current (In) | Main Circuit 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current AC-21A (Ie) | (500 V) 800 A (690 V) 800 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 250 kW (400 V) 450 kW (415 V) 450 kW (500 V) 560 kW (690 V) 710 kW |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 18 kiloampere rms |
| Standards | IEC 60947-3 |
| Switches Operating Mechanism | 03 (Left Side) |
| Terminal Type | Lug terminals |
| Terminal Width | 39 mm |
| Tightening Torque | 50 ... 75 N·m |
| A2L Certificate – IEC | 1SCC311209D0201 |
| ATEX Certificate | No certification needed |
| CCC Certificate | CCC OS630-800 2016 |
| Declaration of Conformity - CE | 1SCC311112D2704 |
| DNV GL Certificate | 1SCC311131D0203 |
| UL Certificate | No certification needed |
| IDEA Granular Category Code (IGCC) | 5291 >> Fuse switch disconnector |
| E-Number (Finland) | 3661540 |
| E-Number (Sweden) | 3172099 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.