AurFort
ABBOTM250E4CM230CABB OTM250E4CM230C, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

SWITCH DISCONNECTOR (AC)

OTM250E4CM230C

SKU 1SCA022846R1910

ABB OTM250E4CM230C: Switch disconnector (AC). Pole configuration: 4P.

4PPoles
OTM250E4CM230CProduct range
Switch disconnector (AC)Product type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 15, 2026.

1SCA022846R1910 — selected manufacturer specifications
Product ID1SCA022846R1910
Catalog DescriptionOTM250E4CM230C MOTORIZED C/O SWITCH
End Of Life Disassembling Instructions1SCC303057M0201
Environmental Information1SCC303036D0202
Environmental Product Declaration - EPD1SCC303095D0201
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC011021D0201
RoHS Declaration1SCC011020D0201
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Data Sheet, Technical Information1SCC303003C0201
Instructions and Manuals1SCC303002M0206
Degree of ProtectionFront IP20
Pollution Degree3
Minimum Order Quantity1 piece
Customs Tariff Number85365080
Country of OriginFinland
Product Net Width307 mm 12.09 in
Product Net Height150 mm 5.91 in
Product Net Depth / Length197 mm 7.76 in
Product Net Weight6.2 kg 13.67 lb
Package Level 1 Unitsbox 1 box
Package Level 1 Width215 mm
Package Level 1 Depth / Length395 mm
Package Level 1 Height215 mm
Package Level 1 Gross Weight7.6 kg
Package Level 1 EAN6417019296876
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 250 A
Conventional Thermal Current (Ithe)Fully Enclosed 250 A
Distance Between PhasesStandard
Fourth Pole PositionRight Side
Fourth Pole TypeSwitched - Simultaneous Function
Handle ColorBlack
Handle TypeDirect Mount
Motor Operational Voltage220 ... 240 V AC
Mounting TypeBase mounting
Number of Poles4P
Operating ModeFront
Position of Line TerminalsTop In - Bottom Out, Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 6.5 W
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-31B (Ie)(380 ... 415 V) 250 A
Rated Operational Current AC-33B (Ie)(380 ... 415 V) 250 A
Rated Operational Power AC-23A (Pe)(380 ... 415 V) 140 kW (500 V) 170 kW (690 V) 250 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 8 kiloampere rms
Switches Operating MechanismMechanism at the End of the Switch
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 15 ... 22 N·m
Transition TypeOpen
Declaration of Conformity - CE1SCC303012D2703
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
E-Number (Finland)3641736