ABBOTM80F4CMA230V

ABB catalog image for this SKU; may represent the product family.
SWITCH DISCONNECTOR (AC)
OTM80F4CMA230V
SKU 1SCA120100R1001ABB OTM80F4CMA230V: Switch disconnector (AC). Pole configuration: 4P.
4PPoles
OTM80F4CMA230VProduct range
Switch disconnector (AC)Product type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 15, 2026.
| Product ID | 1SCA120100R1001 |
|---|---|
| Catalog Description | OTM80F4CMA230V MOTORIZED C/O SWITCH |
| End Of Life Disassembling Instructions | 1SCC303056M0201 |
| Environmental Product Declaration - EPD | 1SCC303135D0201 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Data Sheet, Technical Information | 1SCC303003C0201 |
| Instructions and Manuals | 1SCC303009M0206 |
| Degree of Protection | Front IP20 |
| Pollution Degree | 3 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country of Origin | Finland |
| Product Net Width | 283 mm 11.14 in |
| Product Net Height | 100 mm 3.94 in |
| Product Net Depth / Length | 116 mm 4.57 in |
| Product Net Weight | 1.86 kg 4.1 lb |
| Package Level 1 Units | box 1 box |
| Package Level 1 Width | 115 mm |
| Package Level 1 Depth / Length | 315 mm |
| Package Level 1 Height | 115 mm |
| Package Level 1 Gross Weight | 1.86 kg |
| Package Level 1 EAN | 6417019516882 |
| Cable Cross-Section | 10 ... 70 mm² |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 80 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 80 A |
| Distance Between Phases | Standard |
| Fourth Pole Position | Right Side |
| Fourth Pole Type | Switched - Simultaneous Function |
| Handle Color | Black |
| Handle Type | Direct Mount |
| Motor Operational Voltage | 110 ... 240 V AC/DC |
| Mounting Type | Base mounting |
| Number of Poles | 4P |
| Operating Mode | Front |
| Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Power Loss | at Rated Operating Conditions per Pole 3.5 W |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 800 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 80 A (500 V) 60 A (690 V) 40 A |
| Rated Operational Current AC-31B (Ie) | (380 ... 415 V) 80 A |
| Rated Operational Current AC-33B (Ie) | (380 ... 415 V) 80 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 37 kW (500 V) 37 kW (690 V) 37 kW |
| Rated Operational Voltage | Main Circuit 800 V |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 2.5 kiloampere rms |
| Switches Operating Mechanism | Mechanism at the End of the Switch |
| Terminal Type | Screw Terminals |
| Tightening Torque | acc. IEC 60947-1 6 N·m |
| Transition Type | Open |
| Declaration of Conformity - CE | 1SCC303039D2702 |
| IDEA Granular Category Code (IGCC) | 5208 >> Controller switch |
| E-Number (Finland) | 3601235 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.