AurFort
ABBOT160G03PABB OT160G03P, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

SWITCH DISCONNECTOR (AC)

OT160G03P

SKU 1SCA135139R1001

ABB OT160G03P: Switch disconnector (AC). Pole configuration: 3P.

3PPoles
OT160G03PProduct range
Switch disconnector (AC)Product type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SCA135139R1001 — selected manufacturer specifications
Product ID1SCA135139R1001
Catalog DescriptionOT160G03P SWITCH-DISCONNECTOR
Country of OriginIndia Finland
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
End Of Life Disassembling Instructions1SCC301116M0201
Environmental Information1SCC301267D0201
Environmental Product Declaration - EPD1SCC301281D0201
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC011021D0201
RoHS Declaration1SCC011020D0201
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA1SCC011025D0201
Data Sheet, Technical Information1SCC301020C0201
Instructions and Manuals1SCC301089M0204
Mechanical DrawingsOT160G3_model.igs
Degree of ProtectionFront IP20
Pollution Degree3
Minimum Order Quantity1 piece
Customs Tariff Number85365080
Product Net Width123 mm
Product Net Height130 mm
Product Net Depth / Length73 mm
Product Net Weight0.9 kg
Package Level 1 Unitsbox 1 piece
Package Level 1 Width160 mm 6.3 in
Package Level 1 Depth / Length244 mm 9.6 in
Package Level 1 Height96 mm 3.8 in
Package Level 1 Gross Weight1 kg 2.3 lb
Package Level 1 EAN6417019638706
Cable Cross-SectionCu 10 ... 70 mm²
ColorGrey
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)Fully Enclosed 160 A
Distance Between PhasesStandard
Handle ColorBlack
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles3P
Operating ModeFront and Side
Position of Line TerminalsTop In - Bottom Out Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)(200 A fuse, 500 V) 100 kA (200 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 45 kW (400 ... 415 V) 75 kW (500 V) 90 kW (690 V) 132 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 12 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 4 kA
Special FunctionsNo
StandardsIEC 60947-3 / UL 98 / CSA C22.2 NO.4
Switches Operating MechanismMechanism at the End of the Switch 03 (Left Side)
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 6 N·m
Maximum Operating Voltage UL/CSA600 V
Ampere Rating125 A
Horsepower Rating UL/CSA(240 V AC) Single Phase 20 Hp (440 ... 480 V AC) Single Phase 30 Hp
Tightening Torque UL/CSA53 in·lb
A2L Certificate – IEC1SCC301336D0201
ATEX CertificateNo certification needed
Declaration of Conformity - CE1SCC301210D2701
DNV GL Certificate1SCC301174D0204
UL CertificatecULus certificate OT160G
VDE CertificateNo certification needed
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
E-Number (Finland)3638769
E-Number (Norway)4372122
E-Number (Sweden)3171058

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.