ABBAF190-30-11-13

ABB catalog image for this SKU; may represent the product family.
POWER CONTACTOR, AC SWITCHING
AF190-30-11-13
SKU 1SFL487002R1311ABB AF190-30-11-13: Power contactor, AC switching. Pole configuration: 3P.
3PPoles
AF190-30-11-13Product range
Power contactor, AC switchingProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 08, 2026.
| Product ID | 1SFL487002R1311 |
|---|---|
| Catalog Description | AF190-30-11-13 Contactor |
| Country of Origin | India Georgia China |
| Lead Time | 0 day 55 day 28 day 21 day |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Active Inactive |
| Quote Only | No |
| Stocked At Warehouses | AETAD009EXPU BRABB008EXPU BRAPR001EXPU CHNOR001EXPU CHSEC006EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU CZABB006EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB003EXPU INABB015EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU |
| Configuration Only | No |
| Criticality | No |
| Note | No |
| Product Availability Class | Standard delivery time |
| Storage Location | 4001 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| EPLAN Data | 9AAC174541_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Data Sheet, Technical Information (Part 2) | 1SAC200017M0002 |
| Instructions and Manuals | 1SFC100008M0201 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Product Net Width | 105 mm |
| Product Net Depth / Length | 152 mm |
| Product Net Height | 196 mm |
| Product Net Weight | 2.4 kg |
| Dimension Diagram | 1SFB535001G1056.pdf |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A |
| Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 250 A (1000 V) 60 °C 225 A (1000 V) 70 °C 185 A (690 V) 40 °C 275 A (690 V) 60 °C 250 A (690 V) 70 °C 200 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 190 A (440 V) 60 °C 190 A (500 V) 60 °C 156 A (690 V) 60 °C 85 A (1000 V) 60 °C 85 A (380 / 400 V) 60 °C 190 A (220 / 230 / 240 V) 60 °C 190 A |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 190 A (440 V) 60 °C 190 A (500 V) 60 °C 135 A (690 V) 60 °C 135 A (1000 V) 60 °C 85 A (380 / 400 V) 60 °C 190 A (220 / 230 / 240 V) 60 °C 190 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A (220 V) 3 Poles in Series, 40 °C 250 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A (220 V) 3 Poles in Series, 40 °C 250 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A (220 V) 3 Poles in Series, 40 °C 250 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 90 kW (440 V) 110 kW (500 V) 110 kW (690 V) 132 kW (1000 V) 110 kW (380 / 400 V) 90 kW (220 / 230 / 240 V) 55 kW |
| Rated Operational Power AC-3e (Pe) | (415 V) 90 kW (440 V) 110 kW (500 V) 110 kW (690 V) 132 kW (1000 V) 110 kW (380 / 400 V) 90 kW (220 / 230 / 240 V) 55 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Short-Circuit Protective Devices | gG Type Fuses 355 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 26.8 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 26.8 V·A Holding at Max. Rated Control Circuit Voltage DC 3.5 V·A Holding at Max. Rated Control Circuit Voltage DC 3.5 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 285 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 285 V·A Pull-in at Max. Rated Control Circuit Voltage DC 360 V·A Pull-in at Max. Rated Control Circuit Voltage DC 360 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 9 W at Rated Operating Conditions AC-3 per Pole 4 W |
| Operate Time | Between Coil De-energization and NO Contact Opening 37 ... 47 ms Between Coil Energization and NO Contact Closing 25 ... 55 ms |
| Connecting Capacity Main Circuit | Flexible 2 x 50 ... 95 mm² Rigid Al-Cable 1 x 95 ... 185 mm² Rigid Cu-Cable 1 x 6 ... 150 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Flexible 1 x 6 ... 120 mm² Rigid Al-Cable 1 x 95 ... 185 mm² Rigid Cu-Cable 1 x 6 ... 150 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Tightening Torque | Cable Lug 18 N·m Main Circuit 14 ... 31 N·m |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
| General Use Rating UL/CSA | (1000 V AC) 250 A (600 V AC) 275 A |
| Horsepower Rating UL/CSA | (200 V AC) Three Phase 50 hp (208 V AC) Three Phase 50 hp (220 ... 240 V AC) Three Phase 60 hp (440 ... 480 V AC) Three Phase 125 hp (550 ... 600 V AC) Three Phase 150 hp |
| Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 156 A (550 ... 600 V AC) Three Phase 144 A |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility UL 2799 Zero Waste To Landfill Validation available |
| ABB EcoSolutions Profile | 1SFC100125C0366 |
| End Of Life Disassembling Instructions | 1SFC100112M0001 |
| Environmental Product Declaration - EPD | 1SFC100095D0201 2TFP200018A1001 |
| Extended Product Lifetime | Product Durability is Enhanced |
| Improved Energy Efficiency for Customers | Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 79.1 % |
| A2L Certificate – UL | 9AKK108468A6695 |
| ABS Certificate | 14-LD1092198-PDA 14-LD1092198-1-PDA-DUP |
| BV Certificate | BV_36353_A0BV |
| CB Certificate | SE-82315 |
| CCS Certificate | GB14T00030 GZ15T00069 |
| CQC Certificate | CQC2014010304676685 CQC2014010304724672 |
| cULus Certificate | 20121023-E36588 |
| Declaration of Conformity - CE | 2CMT2015-005439 |
| Declaration of Conformity - UKCA | 2CMT2020-006118 |
| DNV Certificate | DNV_E-14043 |
| LR Certificate | 16-20064 |
| PRS Certificate | TE_2092_880423_16 |
| RINA Certificate | ELE060313XG_002 |
| UL Listing Card | UL_E36588 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 160 mm |
| Package Level 1 Depth / Length | 258 mm |
| Package Level 1 Height | 235 mm |
| Package Level 1 Gross Weight | 3 kg |
| Package Level 1 EAN | 7320500480434 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3706394 |
| E-Number (Norway) | 4117637 |
| E-Number (Sweden) | 3210134 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.