AurFort
ABBAF400-30-11-70ABB AF400-30-11-70, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CONTACTOR, AC SWITCHING

AF400-30-11-70

SKU 1SFL577001R7011

ABB AF400-30-11-70: Power contactor, AC switching. Pole configuration: 3P.

3PPoles
AF400-30-11-70Product range
Power contactor, AC switchingProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

1SFL577001R7011 — selected manufacturer specifications
Product ID1SFL577001R7011
Catalog DescriptionAF400-30-11 100-250V 50/60Hz / 100-250V DC Contactor
Configuration OnlyNo
Country of OriginSweden India
CriticalityNo
Lead Time49 day 999 day
Made To OrderNo
NoteNo
Product Availability ClassStandard delivery time No more available. No replacement
Product Sales StatusActive Inactive
Quote OnlyNo
Stocked At WarehousesBRAPR001EXPU CHNOR001EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB015EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU
Storage Location4001
Warranty ReturnProduct under warranty must be returned
Minimum Order Quantity1 piece
Customs Tariff Number85364900
EPLAN Data9AAC200764_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Data Sheet, Technical Information (Part 2)1SAC200017M0002
Instructions and Manuals1SFC380023-en
CAD Dimensional Drawing2CDC001079B0201
Product Net Width186 mm
Product Net Depth / Length216 mm
Product Net Height278 mm
Product Net Weight10.6 kg
Dimension Diagram53540919-59
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles3P
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 600 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 600 A (1000 V) 55 °C 500 A (1000 V) 70 °C 400 A (690 V) 40 °C 600 A (690 V) 55 °C 500 A (690 V) 70 °C 400 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 400 A (440 V) 55 °C 400 A (500 V) 55 °C 400 A (690 V) 55 °C 350 A (1000 V) 55 °C 155 A (380 / 400 V) 55 °C 400 A (220 / 230 / 240 V) 55 °C 400 A
Rated Operational Current DC-1 (Ie)(110 V) 1-Pole, 40 °C 600 A (110 V) 2 Poles in Series, 40 °C 600 A (220 V) 3 Poles in Series, 40 °C 600 A (600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current DC-3 (Ie)(110 V) 1-Pole, 40 °C 600 A (110 V) 2 Poles in Series, 40 °C 600 A (220 V) 3 Poles in Series, 40 °C 600 A (600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Current DC-5 (Ie)(110 V) 1-Pole, 40 °C 600 A (110 V) 2 Poles in Series, 40 °C 600 A (220 V) 3 Poles in Series, 40 °C 600 A (600 V) 3 Poles in Series, 40 °C 600 A
Rated Operational Power AC-3 (Pe)(415 V) 220 kW (440 V) 220 kW (500 V) 250 kW (690 V) 315 kW (1000 V) 220 kW (380 / 400 V) 200 kW (220 / 230 / 240 V) 110 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Making Capacity AC-310 x Ie AC-3
Short-Circuit Protective DevicesgG Type Fuses 630 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 840 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 3100 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 4400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 2500 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4000 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3500 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour (AC-2 / AC-4) 60 cycles per hour (AC-3) 300 cycles per hour
Mechanical Durability3 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 31 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 31 V·A Holding at Max. Rated Control Circuit Voltage DC 4.3 V·A Holding at Max. Rated Control Circuit Voltage DC 4.3 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 990 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 990 V·A Pull-in at Max. Rated Control Circuit Voltage DC 1100 V·A Pull-in at Max. Rated Control Circuit Voltage DC 1100 W
Power Lossat Rated Operating Conditions AC-1 per Pole 32 W at Rated Operating Conditions AC-3 per Pole 14 W
Operate TimeBetween Coil De-energization and NC Contact Closing 45 ... 55 ms Between Coil De-energization and NO Contact Opening 48 ... 58 ms Between Coil Energization and NC Contact Opening 45 ... 115 ms Between Coil Energization and NO Contact Closing 50 ... 120 ms
Connecting Capacity Main CircuitBar 47 mm² Rigid Al-Cable 2x240 mm² Rigid Cu-Cable 240 mm² Rigid Cu-Cable 2x240 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm²
Connecting CapacityBar 47 mm² Rigid Al-Cable 2x240 mm² Rigid Cu-Cable 2x240 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Connecting Terminals (delivered in open position) Main PolesM 3.5 (+,-) pozidriv 2 screw with cable clamp
Recommended Screw DriverMain Circuit M10 Control Circuit Pozidriv 2 Control Circuit M3.5
Tightening TorqueCable Lug 35 N·m Main Circuit 35 N·m
Terminal TypeMain Circuit: Bars
Suitable for Product ClassBlock ContactorsBlock Contactors
Product NameBlock Contactor
Maximum Operating Voltage UL/CSAMain Circuit 1000 V
General Use Rating UL/CSA(1000 V AC) 550 A (600 V AC) 550 A
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 125 Hp (200 ... 208 V AC) Three Phase 125 hp (200 V AC) Three Phase 125 hp (208 V AC) Three Phase 125 hp (220 ... 240 V AC) Three Phase 150 Hp (220 ... 240 V AC) Three Phase 150 hp (440 ... 480 V AC) Three Phase 350 Hp (440 ... 480 V AC) Three Phase 350 hp (550 ... 600 V AC) Three Phase 400 Hp (550 ... 600 V AC) Three Phase 400 hp
Full Load Amps Motor Use(200 ... 208 V AC) Three Phase 358.8 A (220 ... 240 V AC) Three Phase 360 A (440 ... 480 V AC) Three Phase 414 A (550 ... 600 V AC) Three Phase 382 A
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C Operation -40 ... 70 °C Storage -40 ... +70 °C
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Shock Direction: A 5 g Shock Direction: B1 5 g Shock Direction: B2 5 g Shock Direction: C1 5 g Shock Direction: C2 5 g
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
ABB EcoSolutions Profile1SFC100125C0366
End Of Life Disassembling Instructions1SFC100112M0003
Environmental Product Declaration - EPD1SFC100105D0201 2TFP200031A1001
Extended Product LifetimeProduct Durability is Enhanced
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 63.1 %
ABS Certificate15-LD1408622-PDA
BV CertificateBV_13409-C0BV
CB CertificateSE-82316
CCS CertificateGB14T00030 GZ15T00069
CQC CertificateCQC2007010304256683 CQC2011010304514755
cULus Certificate20121207-E36588
Declaration of Conformity - CE2CMT2019-005796
Declaration of Conformity - UKCA2CMT2020-006118
DNV CertificateTAE00001W1
LOVAG CertificateSE-0146190
LR Certificate16-20064
PRS CertificateTE_2092_880423_16
RINA CertificateELE060313XG_002
UL Listing CardUL_E36588
Package Level 1 Unitsbox 1 piece
Package Level 1 Width280 mm
Package Level 1 Depth / Length375 mm
Package Level 1 Height310 mm
Package Level 1 Gross Weight12 kg
Package Level 1 EAN7320500217665
IDEA Granular Category Code (IGCC)4758 >> Iec Contactors
E-Number (Finland)3709332
E-Number (Norway)4115288
E-Number (Sweden)3228336

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.