ABBAF1350-30-11-70

ABB catalog image for this SKU; may represent the product family.
POWER CONTACTOR, AC SWITCHING
AF1350-30-11-70
SKU 1SFL657001R7011ABB AF1350-30-11-70: Power contactor, AC switching. Pole configuration: 3P.
3PPoles
AF1350-30-11-70Product range
Power contactor, AC switchingProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 08, 2026.
| Product ID | 1SFL657001R7011 |
|---|---|
| Catalog Description | AF1350-30-11 100-250V 50/60Hz / 100-250V DC Contactor |
| Country of Origin | China India |
| Lead Time | 28 day |
| Made To Order | No |
| Warranty Return | Product under warranty must be returned |
| Product Sales Status | Inactive Active |
| Quote Only | No |
| Stocked At Warehouses | INABB015EXPU |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| EPLAN Data | 9AAC200757_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Data Sheet, Technical Information (Part 2) | 1SAC200017M0002 |
| Instructions and Manuals | 1SFC101002M5501 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Product Net Width | 438 mm |
| Product Net Depth / Length | 244 mm |
| Product Net Height | 392 mm |
| Product Net Weight | 32 kg |
| Dimension Diagram | 53540930-7 |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1350 A |
| Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 1350 A (1000 V) 55 °C 1150 A (1000 V) 70 °C 1000 A (690 V) 40 °C 1350 A (690 V) 55 °C 1150 A (690 V) 70 °C 1000 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 860 A (440 V) 55 °C 860 A (500 V) 55 °C 800 A (690 V) 55 °C 800 A (1000 V) 55 °C 375 A (380 / 400 V) 55 °C 860 A (220 / 230 / 240 V) 55 °C 860 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 40 °C 1350 A (600 V) 3 Poles in Series, 40 °C 1350 A (850 V) 3 Poles in Series, 40 °C 1350 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 40 °C 1350 A (600 V) 3 Poles in Series, 40 °C 1350 A (850 V) 3 Poles in Series, 40 °C 1350 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 40 °C 1350 A (600 V) 3 Poles in Series, 40 °C 1350 A (850 V) 3 Poles in Series, 40 °C 1350 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 500 kW (440 V) 560 kW (500 V) 560 kW (690 V) 800 kW (1000 V) 560 kW (380 / 400 V) 475 kW (220 / 230 / 240 V) 257 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 8000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 10000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 6000 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 10000 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 60 cycles per hour (AC-2 / AC-4) 60 cycles per hour (AC-3) 60 cycles per hour |
| Mechanical Durability | 0.5 million |
| Maximum Mechanical Switching Frequency | 60 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 50 Hz / 60 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 75.7 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 75.7 V·A Holding at Max. Rated Control Circuit Voltage DC 14.1 V·A Holding at Max. Rated Control Circuit Voltage DC 14.1 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2545 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2545 V·A Pull-in at Max. Rated Control Circuit Voltage DC 2865 V·A Pull-in at Max. Rated Control Circuit Voltage DC 2865 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 66 W at Rated Operating Conditions AC-3 per Pole 27 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 35 ... 55 ms Between Coil De-energization and NO Contact Opening 35 ... 55 ms Between Coil Energization and NC Contact Opening 50 ... 80 ms Between Coil Energization and NO Contact Closing 50 ... 80 ms |
| Connecting Capacity Main Circuit | Bar 100 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1x 0.75 ... 2.5 mm² Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 1 x 1 .... 4 mm² Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Bar 100 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Connecting Terminals (delivered in open position) Main Poles | M 3.5 (+,-) pozidriv 2 screw with cable clamp |
| Recommended Screw Driver | Main Circuit M12 Control Circuit Pozidriv 2 Control Circuit M3.5 |
| Tightening Torque | Cable Lug 45 N·m Main Circuit 45 N·m |
| Terminal Type | Main Circuit: Bars |
| Suitable for Product Class | Block ContactorsBlock Contactors |
| Product Name | Block Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
| General Use Rating UL/CSA | (1000 V AC) 1350 A (600 V AC) 1350 A |
| Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 400 Hp (220 ... 240 V AC) Three Phase 400 hp (440 ... 480 V AC) Three Phase 800 Hp (440 ... 480 V AC) Three Phase 800 hp (550 ... 600 V AC) Three Phase 1000 Hp (550 ... 600 V AC) Three Phase 1000 hp |
| Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 954 A (550 ... 600 V AC) Three Phase 944 A |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C Operation -40 ... 70 °C Storage -40 ... +70 °C |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| ABB EcoSolutions Profile | 1SFC100125C0366 |
| End Of Life Disassembling Instructions | 1SFC100112M0005 |
| Environmental Product Declaration - EPD | 1SFC100110D0201 2TFP200026A1001 |
| Extended Product Lifetime | Product Durability is Enhanced |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 71.3 % |
| ABS Certificate | 15-LD1408622-PDA |
| BV Certificate | BV_13409-C0BV |
| CB Certificate | SEMKO_SE-74013 |
| CCS Certificate | GB14T00030 GZ15T00069 |
| CQC Certificate | CQC2003010304101933 CQC2015010304752548 |
| cULus Certificate | UL_20130904-E73397 9AKK108469A9188 |
| Declaration of Conformity - CE | 2CMT2019-005796 |
| Declaration of Conformity - UKCA | 2CMT2020-006118 |
| DNV Certificate | TAE00001W1 |
| LOVAG Certificate | SE-202726 |
| LR Certificate | 16-20064 |
| PRS Certificate | TE_2092_880423_16 |
| RINA Certificate | ELE060313XG_002 |
| UL Listing Card | UL_E73397 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 555 mm |
| Package Level 1 Depth / Length | 365 mm |
| Package Level 1 Height | 500 mm |
| Package Level 1 Gross Weight | 34 kg |
| Package Level 1 EAN | 7320500250143 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3709257 |
| E-Number (Norway) | 4115388 |
| E-Number (Sweden) | 4115388 |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.