ABBAF2650-30-11-70

ABB catalog image for this SKU; may represent the product family.
POWER CONTACTOR, AC SWITCHING
AF2650-30-11-70
SKU 1SFL667001R7011ABB AF2650-30-11-70: Power contactor, AC switching. Pole configuration: 3P.
3PPoles
AF2650-30-11-70Product range
Power contactor, AC switchingProduct type
PRODUCT DATA
Technical specifications
Source: ABB English regional product catalog.
Verified September 08, 2026.
| Product ID | 1SFL667001R7011 |
|---|---|
| Catalog Description | AF2650-30-11 100-250V 50/60Hz / 100-250 DC Contactor |
| Configuration Only | No |
| Country of Origin | Sweden |
| Criticality | No |
| Lead Time | 35 day 0 day |
| Made To Order | No |
| Note | No |
| Product Availability Class | Standard delivery time |
| Product Sales Status | Active |
| Quote Only | No |
| Stocked At Warehouses | BRAPR001EXPU CHNOR001EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU ZATAD021EXPU |
| Storage Location | 4001 |
| Warranty Return | Product under warranty must be returned |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| EPLAN Data | 9AAC174543_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Data Sheet, Technical Information (Part 2) | 1SAC200017M0002 |
| Instructions and Manuals | 1SFC101050M0201 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Product Net Width | 438 mm |
| Product Net Depth / Length | 244 mm |
| Product Net Height | 422 mm |
| Product Net Weight | 43 kg |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 2650 A |
| Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 2650 A (1000 V) 55 °C 2350 A (1000 V) 70 °C 2120 A (690 V) 40 °C 2650 A (690 V) 55 °C 2350 A (690 V) 70 °C 2120 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 1-Pole, 70 °C 2650 A (110 V) 2 Poles in Series, 70 °C 2650 A (110 V) 3 Poles in Series, 70 °C 2650 A (220 V) 3 Poles in Series, 40 °C 2650 A (220 V) 3 Poles in Series, 70 °C 2650 A (260 V) 3 Poles in Series, 70 °C 2650 A (300 V) 3 Poles in Series, 70 °C 2650 A (340 V) 3 Poles in Series, 70 °C 2650 A (600 V) 3 Poles in Series, 40 °C 2650 A (72 V) 1-Pole, 70 °C 2650 A (72 V) 2 Poles in Series, 70 °C 2650 A (72 V) 3 Poles in Series, 70 °C 2650 A (850 V) 3 Poles in Series, 40 °C 2650 A |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 10000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 2800 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 5500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 12000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 7500 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 8400 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 12 kV |
| Maximum Electrical Switching Frequency | (AC-1) 15 cycles per hour |
| Mechanical Durability | 0.3 million |
| Maximum Mechanical Switching Frequency | 60 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 75.7 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 75.7 V·A Holding at Max. Rated Control Circuit Voltage DC 14.1 V·A Holding at Max. Rated Control Circuit Voltage DC 14.1 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2545 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2545 V·A Pull-in at Max. Rated Control Circuit Voltage DC 2865 V·A Pull-in at Max. Rated Control Circuit Voltage DC 2865 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 198 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 35 ... 55 ms Between Coil De-energization and NO Contact Opening 35 ... 55 ms Between Coil Energization and NC Contact Opening 50 ... 80 ms Between Coil Energization and NO Contact Closing 50 ... 80 ms |
| Connecting Capacity Main Circuit | Bar 100 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Bar 100 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Connecting Terminals (delivered in open position) Main Poles | M 3.5 (+,-) pozidriv 2 screw with cable clamp |
| Recommended Screw Driver | Main Circuit M12 Control Circuit Pozidriv 2 Control Circuit M3.5 |
| Tightening Torque | Cable Lug 45 N·m Main Circuit 45 N·m |
| Terminal Type | Main Circuit: Bars |
| Suitable for Product Class | Block ContactorsBlock Contactors |
| Product Name | Block Contactor |
| Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
| General Use Rating UL/CSA | (1000 V AC) 2700 A (600 V AC) 2700 A |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C Operation -40 ... 70 °C Storage -40 ... +70 °C |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| ABB EcoSolutions Profile | 1SFC100125C0366 |
| End Of Life Disassembling Instructions | 1SFC100112M0005 |
| Environmental Product Declaration - EPD | 1SFC100110D0201 2TFP200026A1001 |
| Extended Product Lifetime | Product Durability is Enhanced |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 71.3 % |
| ABS Certificate | 15-LD1408622-PDA |
| BV Certificate | BV_13409-C0BV |
| CB Certificate | SEMKO_SE70500M1 |
| CCS Certificate | GB14T00030 GZ15T00069 |
| CQC Certificate | CQC2013010304604054 CQC2017010304970103 |
| cULus Certificate | 9AKK107046A8617 |
| Declaration of Conformity - CE | 2CMT2019-005796 |
| Declaration of Conformity - UKCA | 2CMT2020-006118 |
| DNV Certificate | TAE00001W1 |
| LR Certificate | 16-20064 |
| RINA Certificate | ELE060313XG_002 |
| UL Listing Card | UL_E73397 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 555 mm |
| Package Level 1 Depth / Length | 365 mm |
| Package Level 1 Height | 500 mm |
| Package Level 1 Gross Weight | 45 kg |
| Package Level 1 EAN | 7320500481431 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.