VOLTAGE MONITORING RELAY

CM-ESS.MS

SKU 1SVR730830R0500

ABB CM-ESS.MS: Voltage monitoring relay.

CM-ESS.MSProduct range
Voltage monitoring relayProduct type
1SVR730830R0500Reference
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

1SVR730830R0500 — selected manufacturer specifications
Product ID1SVR730830R0500
Catalog DescriptionCM-ESS.MS Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC
Country of OriginGermany
Lead Time0 day 10 day 160 day
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesAETAD009EXPU BRABB008EXPU BRAPR001EXPU CHNOR001EXPU CHSEC006EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU CZABB004EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU USABB251EXPU ZATAD021EXPU
Configuration OnlyNo
CriticalityNo
NoteNo
Product Availability ClassStandard delivery time
Storage Location4001
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Data Sheet, Technical Information2CDC112173D0201
Instructions and Manuals1SVC730710M1000 1SVC730710M0000
CAD Dimensional Drawing2CDC001079B0201
EPLAN Data9AAC132594_EPLAN
Product Net Width22.5 mm
Product Net Height85.6 mm
Product Net Depth / Length103.7 mm
Product Net Weight0.154 kg
FunctionOver- or undervoltage monitoring
Measuring Range3 ... 30 V 6 ... 60 V 30 ... 300 V 60 ... 600 V
Time RangeTripping Delay (ON) 0 s
Rated Control Supply Voltage (Us)24 ... 240 V AC/DC
Output2 C/O (SPDT) Contacts, Operating Principle Selectable
Terminal TypeScrew Terminals
Rated Operational Current AC-12 (Ie)(230 V) 4 A
Rated Operational Current AC-15 (Ie)(230 V) 3 A
Rated Operational Current DC-12 (Ie)(24 V) 4 A
Rated Operational Current DC-13 (Ie)(24 V) 2 A
Minimum Switching Capacity24 V 10 mA
Rated Impulse Withstand Voltage (Uimp)Measuring Circuit / Output Circuit 6 kV Output Circuit 1 / Output Circuit 2 4 kV Supply Circuit / Measuring Circuit 6 kV Supply Circuit / Output Circuit 4 kV
Rated Insulation Voltage (Ui)Measuring Circuit / Output Circuit 600 V Output Circuit 1 / Output Circuit 2 250 V Supply Circuit / Measuring Circuit 600 V Supply Circuit / Output Circuit 250 V
Degree of ProtectionHousing IP50 Terminals IP20
Overvoltage CategoryIII
Pollution Degree3
Short-Circuit Protective DevicesOutput Circuit NC - F Type Fuses 10 A Output Circuit NO - F Type Fuses 10 A
Electrical DurabilityAC-12 100000 cycle
Mechanical DurabilityNr. Operations 30000000 cycle
Connecting CapacityFlexible with Ferrule 1x 0.5 ... 2.5 mm² Flexible with Ferrule 2x 0.5 ... 1.5 mm² Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² Flexible 1x 0.5 ... 2.5 mm² Flexible 2x 0.5 ... 1.5 mm² Rigid 1x 0.5 ... 4 mm² Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque0.6 ... 0.8 N·m
Wire Stripping Length8 mm
Recommended Screw Driver0.8 x 4 4.5 Pozidriv 1
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
StandardsCAN/CSA C22.2 No.14 IEC/EN 63000 IEC/EN 60255-27 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508
Maximum Operating Voltage UL/CSAOutput Circuit 300 V AC
Contact Rating UL/CSAB300
Connecting Capacity UL/CSAFlexible 1x 18-14 AWG Flexible 2x 18-16 AWG Rigid 1x 20-12 AWG Rigid 2x 20-14 AWG
Tightening Torque UL/CSA7.08 in·lb
Pilot Duty UL/CSAB300
Flammability According to UL94V-0
Ambient Air TemperatureOperation -20 ... +60 °C Storage -40 ... +85 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SVD981001-4501
RoHS Declaration1SVD981001-4401
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006536
ABB EcoSolutionsYes
ABB EcoSolutions Profile1SFC100125C0416
Environmental Product Declaration - EPD1SAC200438H0001
CB CertificateCB_DK-28255-UL
cULus CertificatecULus508_20120203-E140448
Declaration of Conformity - CCC2020980303000196
Declaration of Conformity - CE1SVD981013-00
Declaration of Conformity - UKCA1SVD981013-10
DNV GL CertificateDVN_GL_TAA0000292
Package Level 1 Unitsbox 1 piece
Package Level 1 Width97 mm
Package Level 1 Depth / Length30 mm
Package Level 1 Height109 mm
Package Level 1 Gross Weight0.176 kg
Package Level 1 EAN4016779852173
E-Number (Finland)2712254
E-Number (Norway)4188090
E-Number (Sweden)3860620

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.