AurFort
VigiPacTSchneider Electric residual current protection relay, Vigirex RH197M, 30 mA to 30 A, 220/240 VAC 50/60Hz, alarm 50% or 100%, DIN rail mounting, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

RESIDUAL CURRENT PROTECTION RELAY

residual current protection relay, Vigirex RH197M, 30 mA to 30 A, 220/240 VAC 50/60Hz, alarm 50% or 100%, DIN rail mounting

SKU 56517

Schneider Electric 56517 is a residual current protection relay in the VigiPacT range. Key specifications include signal contacts: 1 NO; mounting support: DIN rail; ip protection: IP40 on front face: conforming to EN/IEC 60529.

1 NOSignal contacts
DIN railMounting support
IP40 on front face: conforming to EN/IEC 60529IP protection
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

56517 — selected manufacturer specifications
Product reference56517
RangeVigiPacT
Device short nameRH197M
Product or component typeResidual current protection relay
Relay applicationProtection relay
Mounting supportDIN rail
Earth-leakage protection classType A
Type of settingSelector
Residual earth-leakage sensitity adjustment typeAdjustable 19 settings
Earth-leakage sensitivity0.03…30 A
Earth-leakage time delayInstantaneous for 0.03 A Adjustable 7 settings 0…4.5 s for 0.03…30 A
Alarm threshold100 % 50 %
Current sensors compatibilityVigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current8 A
Minimum load10 mA at 12 V
[Us] rated supply voltage220...240 V AC 50/60 Hz 70...110 %
Power consumption in VA4 VA
Monitored distribution system1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum)
Earthing systemTT TN-S IT
[Uimp] rated impulse withstand voltage8 kV
ResetManual reset Automatic reset
Test functionLocal Remote test
MonitoringElectronics (watchdog) Power supply (continuous) Relay/sensor link (continuous)
Signal contacts composition1 NO
Type of measurementEarth fault current internal measurement, range: 80...100 %
Refresh time0.5 s
Tamperproof of settingsProtected by sealable cover
Connections - terminalsAuxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible 24 AWG...12 AWG Fault: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG Fault: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG Fault: terminal block cable(s) 0.25…2.5 mm² flexible 24 AWG...12 AWG Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG Relay test and fault reset: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG Relay test and fault reset: terminal block cable(s) 0.25…2.5 mm² flexible 24 AWG...12 AWG Sensor: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG Sensor: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG Sensor: terminal block cable(s) 0.25…2.5 mm² flexible 24 AWG...12 AWG Voltage presence: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG Voltage presence: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG Voltage presence: terminal block cable(s) 0.25…2.5 mm² flexible 24 AWG...12 AWG
Wire stripping lengthAuxiliary power supply: 7 mm Fault: 7 mm Relay test and fault reset: 7 mm Sensor: 7 mm Voltage presence: 7 mm
Tightening torqueAuxiliary power supply: 0.6 N.m Fault: 0.6 N.m Relay test and fault reset: 0.6 N.m Sensor: 0.6 N.m Voltage presence: 0.6 N.m
9 mm pitches8
StandardsEN/IEC 60947-2 Annex M EN/IEC 60755
Width71.2 mm
Height98.7 mm
Depth65.8 mm
Net weight0.3 kg
IP degree of protectionIP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protectionIK07 conforming to EN 50102
Mechanical robustnessFire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm
Overvoltage categoryIV
Electrical shock protection classClass II
Electromagnetic compatibilityConducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity95 % at 55 °C
Pollution degree3 conforming to IEC 60664-1
Ambient air temperature for operation-25…55 °C
Ambient air temperature for storage-40…85 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.