Schneider Electric catalog image for this SKU; may represent the product family.
CONTACTOR
contactor iCT - 2 poles - 2 NO - 40 A - 220..240 V AC
SKU A9C20842Schneider Electric A9C20842 is a contactor in the Acti9 iCT range. Key specifications include operational current: 40 A AC-7A; contact configuration: 2 NO; control voltage: 220...240 V AC 50 Hz.
40 A AC-7AOperational current
2 NOContact configuration
220...240 V AC 50 HzControl voltage
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 17, 2026.
| Product reference | A9C20842 |
|---|---|
| range of product | Acti9 |
| Product name | Acti9 iCT |
| Product or component type | Contactor |
| Device short name | iCT |
| Device application | Motor-heating-lighting |
| Poles | 2P |
| [Ie] rated operational current | 40 A AC-7A 15 A AC-7B |
| Pole contact composition | 2 NO |
| Network type | AC |
| Control type | Remote control |
| [Uc] control circuit voltage | 220...240 V AC 50 Hz |
| Network frequency | 50 Hz |
| [Ue] rated operational voltage | 250 V AC 50 Hz |
| Maximum power | 1.6 W at 250 V AC |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Control signal type | Maintained |
| Switching frequency | 100 switching operations/day |
| Local signalling | Action indicator |
| Hold-in power consumption in VA | 4.6 VA |
| Inrush power in VA | 34 VA |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| 9 mm pitches | 4 |
| Height | 85 mm |
| Width | 36 mm |
| Depth | 60 mm |
| Colour | White |
| Mechanical durability | 1000000 cycles |
| Electrical durability | 100000 cycles IEC/EN 61095 40 A 50 Hz AC-7A 30000 cycles IEC/EN 61095 15 A 50 Hz AC-7B 30000 cycles IEC/EN 61095 50 Hz AC-7C 100000 cycles EN/IEC 60947-4-1 50 Hz AC-1 30000 cycles EN/IEC 60947-4-1 50 Hz AC-3 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a 30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b |
| Connections - terminals | Control circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid Power circuit: tunnel type terminals1 cable(s) 6…16 mm² flexible Power circuit: tunnel type terminals1 cable(s) 6…25 mm² rigid Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible |
| Tightening torque | Control circuit: 0.8 N.m Power circuit: 3.5 N.m |
| Product compatibility | IACTc IACTs IACTp IATEt |
| Compatibility code | ICT |
| Market segment | Small commercial Residential |
| Standards | IEC/EN 61095 |
| Noise level | 30 dB |
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 2 |
| Tropicalisation | 2 conforming to EN 60947-4-1 2 conforming to EN 61095 2 conforming to IEC 1095 |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -5…60 °C |
| Ambient air temperature for storage | -40…70 °C |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.