AurFort
Acti9 iCTSchneider Electric iCT 100A 4NO 220...240V 50Hz contactor, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACTOR

iCT 100A 4NO 220...240V 50Hz contactor

SKU A9C20884

Schneider Electric A9C20884 is a contactor in the Acti9 iCT range. Key specifications include operational current: 100 A AC-7A; contact configuration: 4 NO; control voltage: 220...240 V AC 50 Hz.

100 A AC-7AOperational current
4 NOContact configuration
220...240 V AC 50 HzControl voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

A9C20884 — selected manufacturer specifications
Product referenceA9C20884
range of productActi9
Product nameActi9 iCT
Product or component typeContactor
Device short nameiCT
Device applicationHeating-low inductive load
Poles4P
[Ie] rated operational current100 A AC-7A
Pole contact composition4 NO
Network typeAC
Utilisation categoryAC-1 conforming to EN 60947-4-1 AC-7A conforming to EN 61095 AC-7A conforming to IEC 61095 AC-7A conforming to UTE C 61-481 AC-1 conforming to IEC 60947-4-1
Control typeRemote control
[Uc] control circuit voltage220...240 V AC 50 Hz
Network frequency50 Hz
[Ue] rated operational voltage400 V AC 50 Hz
Maximum powerAC-7A: 4.2 W at 400 V AC 50 Hz
[Ui] rated insulation voltage500 V AC 50 Hz
[Uimp] rated impulse withstand voltage4 kV
Control signal typeMaintained
Switching frequency100 switching operations/day
Local signallingAction indicator
Hold-in power consumption in VA13 VA
Inrush power in VA106 VA
Mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
9 mm pitches12
Height85 mm
Width108 mm
Depth60 mm
ColourWhite
Electrical durability30000 cycles EN 61095 400 V 16 A AC 50 Hz AC-7A 30000 cycles UTE C 61-481 400 V 6 A AC 50 Hz AC-7A 30000 cycles IEC 61095 400 V AC 50 Hz AC-7A
Connections - terminalsControl circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible Power circuit: tunnel type terminals1 cable(s) 6…35 mm² solid or flexible
Tightening torquePower circuit: 3.5 N.m Control circuit: 0.8 N.m A1 / A2
Product compatibilityIACTp IACTs IATEt IACTc
Compatibility codeICT
Market segmentSmall commercial Residential
StandardsEN 61095 IEC 61095 UTE C 61-481
Noise level30 dB
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Tropicalisation2 conforming to EN 60947-4-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-5…60 °C
Ambient air temperature for storage-40…70 °C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.