AurFort
TeSys CADSchneider Electric TeSys D control relay - 3 NO + 2 NC - <= 690 V - 24 V AC standard coil, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTROL RELAY

TeSys D control relay - 3 NO + 2 NC - <= 690 V - 24 V AC standard coil

SKU CAD32B7

Schneider Electric CAD32B7 is a control relay in the TeSys CAD range. Key specifications include contact configuration: 3 NO + 2 NC; control voltage: 24 V AC 50/60 Hz; operational voltage: <= 690 V AC 25...400 Hz.

3 NO + 2 NCContact configuration
24 V AC 50/60 HzControl voltage
<= 690 V AC 25...400 HzOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

CAD32B7 — selected manufacturer specifications
Product referenceCAD32B7
RangeTeSys TeSys Deca
Product nameTeSys CAD
Product or component typeControl relay
Device short nameCAD
Contactor applicationControl circuit
Utilisation categoryAC-14 AC-15 DC-13
Pole contact composition3 NO + 2 NC
[Ue] rated operational voltage<= 690 V AC 25...400 Hz
Control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage24 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
[Ith] conventional free air thermal current10 A (at 60 °C)
Irms rated making capacity140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current100 A - 1 s 120 A - 500 ms 140 A - 100 ms
Associated fuse rating10 A gG conforming to IEC 60947-5-1
[Ui] rated insulation voltage600 V UL certified 600 V CSA certified 690 V conforming to IEC 60947-5-1
Mounting supportPlate Rail
Connections - terminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Tightening torque1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Operating time12...22 ms coil energisation and NO closing 4...12 ms coil de-energisation and NO opening 4...19 ms coil energisation and NC opening 6...17 ms coil de-energisation and NC closing
Mechanical durability30 Mcycles
Maximum operating rate180 cyc/mn
Inrush power in VA70 VA 50 Hz (at 20 °C)
Hold-in power consumption in VA8 VA 50 Hz (at 20 °C)
Minimum switching voltage17 V
Minimum switching current5 mA
Non-overlap time1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact
Insulation resistance> 10 MOhm
Mechanical robustnessShocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Height77 mm
Width45 mm
Depth84 mm
Net weight0.58 kg
StandardsEN/IEC 60947-5-1 GB/T 14048.5 UL 60947-5-1 CSA C22.2 No 60947-5-1 JIS C8201-5-1
Product certificationsCB CCC UL CSA EAC CE UKCA
IP degree of protectionIP2X front face conforming to VDE 0106
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-40…60 °C 60…70 °C with derating
Ambient air temperature for storage-60…80 °C
Operating altitude0...3000 m

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.