AurFort
Easy TeSys Control RelaySchneider Electric EasyPact TVS control relay - 2 NO + 2 NC <= 690 V - 24 VAC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTROL RELAY

EasyPact TVS control relay - 2 NO + 2 NC <= 690 V - 24 VAC

SKU CAE22B5

Schneider Electric CAE22B5 is a control relay in the Easy TeSys Control Relay range. Key specifications include contact configuration: 2 NO + 2 NC; control voltage: 24 V AC 50 Hz; operational voltage: <= 690 V AC.

2 NO + 2 NCContact configuration
24 V AC 50 HzControl voltage
<= 690 V ACOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

CAE22B5 — selected manufacturer specifications
Product referenceCAE22B5
RangeEasy TeSys
Range of productEasy TeSys Control Relay
Product or component typeControl relay
Device short nameCAE
Contactor applicationControl circuit
ColourGrey (RAL 7011)
Utilisation categoryAC-15 AC-14
Pole contact composition2 NO + 2 NC
[Ue] rated operational voltage<= 690 V AC
Control circuit typeAC at 50 Hz
[Uc] control circuit voltage24 V AC 50 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
[Ith] conventional free air thermal current10 A (at 40 °C)
Irms rated making capacity140 A at 690 V AC conforming to IEC 60947-5-1
[Icw] rated short-time withstand current120 A - 500 ms 140 A - 100 ms
Associated fuse rating10 A gG at 690 V conforming to IEC 60947-5-1
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1
Mounting supportRail Plate
Connections - terminalsScrew clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end Screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end Screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end
Recommended tightening torque1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz Drop-out: 0.3...0.6 Uc
Operating time4...19 ms coil energisation and NC opening 12...22 ms coil energisation and NO closing 4...12 ms coil de-energisation and NC opening 6...17 ms coil de-energisation and NO closing
Mechanical durability10 Mcycles
Maximum operating rate180 cyc/mn
Inrush power in VA70 VA 50 Hz (at 20 °C)
Hold-in power consumption in VA8 VA 50 Hz (at 20 °C)
Minimum switching voltage17 V
Minimum switching current5 mA
Non-overlap time1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact
Insulation resistance> 10 MOhm
Mechanical robustnessShocks control relay open: 7 Gn for 11 ms Shocks control relay closed: 10 Gn for 11 ms Vibrations control relay open: 1.5 Gn, 5...300 Hz Vibrations control relay closed: 3 Gn, 5...300 Hz
Height74 mm
Width45 mm
Depth80 mm
Net weight0.28 kg
StandardsEN/IEC 60947-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.5 IS/IEC 60947-1 IS/IEC 60947-5-1
Product certificationsCB Scheme CCC CE EAC BIS
IP degree of protectionIP2X conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for operation-20…70 °C
Ambient air temperature for storage-60…80 °C
Operating altitude3000 m without derating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.