AurFort
ABBCA6-11KABB CA6-11K, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

AUXILIARY CONTACT BLOCK

CA6-11K

SKU GJL1201317R0001

ABB CA6-11K: Auxiliary contact block. Pole configuration: 2P.

2PPoles
CA6-11KProduct range
Auxiliary contact blockProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 08, 2026.

GJL1201317R0001 — selected manufacturer specifications
Product IDGJL1201317R0001
Catalog DescriptionCA6-11K Auxiliary Contact 1NO/1NC screw terminal, side mounted
Configuration OnlyNo
Country of OriginChina Finland
CriticalityNo
Lead Time37 day 0 day
Made To OrderNo
NoteNo
Product Availability ClassOn Request, Both availability and price will be quoted case by case. Check the replacement/alternative part
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesBRAPR001EXPU CHNOR001EXPU CLABB001EXPU CNIAB001EXPU COABB001EXPU DEAPRMLCEXPU DKSER001EXPU DUABB001EXPU DUABB003EXPU EESER001EXPU EGAUT001EXPU ESATD001EXPU FISER001EXPU FRAUT001EXPU GBINS001EXPU GRABB001EXPU INABB039EXPU INABBRLCEXPU ITIND002EXPU NLABB021EXPU NOATDRLCEXPU SGIND002EXPU TRDMD001EXPU ZATAD021EXPU
Storage Location4001
Warranty ReturnProduct under warranty must be returned
Minimum Order Quantity1 piece
Customs Tariff Number85365080
EPLAN Data9AAC166197_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Instructions and Manuals2CDC102047M6801
CAD Dimensional Drawing2CDC001079B0201
Product Net Width20.3 mm
Product Net Depth / Length46.5 mm
Product Net Height48.5 mm
Product Net Weight0.03 kg
Dimension DiagramGJL1200443F0001
Number of Main Contacts NO0
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles2P
StandardsIEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L
Rated Operational VoltageAuxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC
Rated Frequency (f)Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC
Conventional Free-air Thermal Current (Ith)Auxiliary Circuit 6 A
Rated Operational Current AC-15 (Ie)(24 V) 4 A (240 V) 4 A (500 V) 2 A (380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 1.5 A (110 V) 0.4 A (220 / 240 V) 0.04 A
Short-Circuit Protective DevicesgG Type Fuses 10 A
Rated Insulation Voltage (Ui)690 V
Rated Impulse Withstand Voltage (Uimp)Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency(AC-15) 600 cycles per hour (DC-13) 600 cycles per hour
Minimum Switching Capacity17 V 5 mA
Power Lossat Rated Operating Conditions per Pole 0.27 W
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 1 ... 2.5 mm² Flexible 1/2x 1 ... 2.5 mm² Rigid 1/2x 1 ... 4 mm²
Wire Stripping LengthAuxiliary Circuit 9 mm
Degree of ProtectionIP20
Tightening TorqueAuxiliary Circuit 0.8 ... 1.1 N·m
Terminal TypeScrew Terminals
Suitable ForK6 KC6
Suitable for Product ClassMini Contactors
Product NameAuxiliary Contact
Maximum Operating Voltage UL/CSA600 V AC
General Use Rating UL/CSA(600 V AC) 5 A
Connecting Capacity Auxiliary Circuit UL/CSAStranded 1/2x 22-10 AWG
Contact Rating UL/CSAA600
Tightening Torque UL/CSAAuxiliary Circuit 7 in·lb
Ambient Air TemperatureOperation -25 ... +55 °C Storage -40 ... +80 °C
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 15g
Resistance to Vibrations5g 5 ... 150 Hz
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
A2L Certificate – IEC1SAA938000-4601
CB Certificate1SAA938001-2001
CCC Certificate2024010305658959
cULus CertificatecUL_E48139
Declaration of Conformity - CE1SAD101100-3101
Declaration of Conformity - UKCA1SAD201100-3101
RMRS Certificate1SAA938001-0704
UL CertificateUL_E48139
Package Level 1 Unitsbox 10 piece
Package Level 1 Width112 mm
Package Level 1 Depth / Length142 mm
Package Level 1 Height62 mm
Package Level 1 Gross Weight0.365 kg
Package Level 1 EAN4013614412080
IDEA Granular Category Code (IGCC)4743 >> Auxiliary contact block
E-Number (Finland)3709107
E-Number (Norway)4190575
E-Number (Sweden)3210099

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.