Schneider Electric catalog image for this SKU; may represent the product family.
MOTOR CIRCUIT BREAKER
Motor circuit breaker, TeSys GV6, 3P, 320A, Icu 70kA, thermal magnetic
SKU GV6P320HSchneider Electric GV6P320H is a motor circuit breaker in the TeSys GV6 range. Key specifications include rated current: 320 A at 65 °C; poles: 3P; operational voltage: 690 V AC 50/60 Hz.
320 A at 65 °CRated current
3PPoles
690 V AC 50/60 HzOperational voltage
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 06, 2026.
| Product reference | GV6P320H |
|---|---|
| Range | TeSys |
| Range of product | TeSys GV6 |
| Device short name | GV6P |
| Product name | TeSys GV6 TeSys Giga |
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Electronic |
| Poles description | 3P |
| Utilisation category | Category A conforming to IEC 60947-2 |
| Motor power kW | 132…160 kW at 400/415 V AC 50/60 Hz 160…200 kW at 500 V AC 50/60 Hz 200…250 kW at 660/690 V AC 50/60 Hz |
| Breaking capacity | 70 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Direct rotary handle |
| [In] rated current | 320 A at 65 °C |
| Magnetic tripping current | 4800 A |
| Rated conditional short-circuit current | 60 kA at 440 V |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current | 320 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Power dissipation per pole | 19.2 W |
| Mechanical durability | 15000 cycles |
| Electrical durability | 5000 cycles for AC-3 at 415 V opening 5000 cycles for AC-3 at 415 V closing |
| maximum operating rate | 25 cyc/h |
| Rated duty | Continuous |
| Connection pitch | 45 mm without spreaders |
| Connections - terminals | Bars Lugs |
| Tightening torque | 50 N.m M10 screw type |
| Mechanical robustness | Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Height | 255 mm |
| Width | 140 mm |
| Depth | 179 mm |
| Net weight | 6.5 kg |
| Colour | Anthracite (RAL 7016) |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 |
| Product certifications | IECEE CB Scheme EAC (pending) |
| Climatic withstand | conforming to IACS E10 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for storage | -50…85 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Operating altitude | 5000 m |
| Ambient air temperature for operation | -25…70 °C |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.
Browse circuit breakers →Browse motor protection circuit breakers →