Schneider Electric LADT4 is a time delay auxiliary contact block in the TeSys Deca range. Key specifications include contact configuration: 1 NO + 1 NC; operational voltage: 690 V AC 25...400 Hz; ip protection: IP20 conforming to IEC 60529.

1 NO + 1 NCContact configuration
690 V AC 25...400 HzOperational voltage
IP20 conforming to IEC 60529IP protection
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

LADT4 — selected manufacturer specifications
Product referenceLADT4
RangeTeSys TeSys Deca
Product nameTeSys Deca
Product or component typeTime delay auxiliary contact block
Range compatibilityTeSys Deca CAD TeSys Deca LC1D TeSys F LC1F TeSys F CR1F
Mounting locationFront
Pole contact composition1 NO + 1 NC
Contacts operationTime delay
Timer typeOn delay
Time delay range10...180 s
[Ue] rated operational voltage690 V AC 25...400 Hz
[Ie] rated operational current6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13
[Ui] rated insulation voltage690 V conforming to IEC 60947-5-1 600 V conforming to UL 60947-5-1 600 V conforming to CSA C22.2 No 60947-5-1
[Ith] conventional free air thermal current10 A (at 60 °C)
StandardsEN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 EN 50012 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ
Product certificationsIECEE CB Scheme UL CSA CCC EAC UKCA
Irms rated making capacity140 A at <= 690 V AC conforming to IEC 60947-5-1 250 A at <= 690 V DC conforming to IEC 60947-5-1
Permissible short-time rating100 A 60 °C 1 s 120 A 60 °C 500 ms 140 A 60 °C 100 ms
Protection typeGG fuse 10 A
Mechanical durability5 Mcycles
Minimum switching current5 mA
Minimum switching voltage17 V
Non-overlap time1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact
Insulation resistance> 10 MOhm
Connections - terminalsScrew clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid Screw clamp terminals
Tightening torque1.7 N.m - with screwdriver flat Ø 6 mm 1.7 N.m - with screwdriver Philips No 2 1.7 N.m - with screwdriver pozidriv No 2
Height48 mm
Width44 mm
Depth61 mm
ColourDark grey
Environmental characteristicNormal environment
IP degree of protectionIP20 conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068
Ambient air temperature for storage-60…80 °C
Ambient air temperature for operation-40…70 °C
Operating altitude3000 m

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.