Schneider Electric catalog image for this SKU; may represent the product family.
AUXILIARY CONTACT BLOCK
Auxiliary contact block,TeSys Giga contactor,2NO,lateral face side mounting,push-in terminals L1/R1
SKU LAG8N203PSchneider Electric LAG8N203P is a auxiliary contact block in the TeSys G range. Key specifications include contact configuration: 2 NO; operational voltage: 600 V AC 25...400 Hz; ip protection: IP20 conforming to IEC 60529.
2 NOContact configuration
600 V AC 25...400 HzOperational voltage
IP20 conforming to IEC 60529IP protection
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 06, 2026.
| Product reference | LAG8N203P |
|---|---|
| Range compatibility | TeSys G LC1G |
| Range of product | TeSys G |
| Range | TeSys |
| Device short name | LAG8N |
| Product or component type | Auxiliary contact block |
| Auxiliary contacts operation | Instantaneous |
| Pole contact composition | 2 NO |
| Connections - terminals | Screw clamp terminals0.75…2.5 mm²solid stranded without cable end Screw clamp terminals0.75…2.5 mm²flexible with cable end |
| Mounting location | Side |
| [Ui] rated insulation voltage | 600 V conforming to IEC 60947-5-1 600 V - certifications CSA 600 V - certifications UL |
| [Ue] rated operational voltage | 600 V AC 25...400 Hz |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 |
| Permissible short-time rating | 100 A 60 °C 1 s 120 A 60 °C 500 ms 140 A 60 °C 100 ms |
| Protection type | GG fuse 10 A |
| Mechanical durability | 8 Mcycles |
| Minimum switching current | 1 mA |
| Minimum switching voltage | 17 V |
| Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Height | 55.8 mm |
| Width | 15.4 mm |
| Depth | 84.8 mm |
| Net weight | 0.05 kg |
| Standards | EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB 14048.5 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme CCC cULus CE UKCA |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Protective treatment | TH |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 3000 m |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.