AurFort
TeSys DecaSchneider Electric Contactor, Tesys Deca, 3P(3NO), AC-3/AC-3e, <=440V 18A, 24V DC coil, screw clamp terminals, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACTOR

Contactor, Tesys Deca, 3P(3NO), AC-3/AC-3e, <=440V 18A, 24V DC coil, screw clamp terminals

SKU LC1D18BD

Schneider Electric LC1D18BD is a contactor in the TeSys Deca range. Key specifications include operational current: 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; contact configuration: 3 NO; control voltage: 24 V DC.

18 A (at <60 °C) at <= 440 V AC AC-3 for power circuitOperational current
3 NOContact configuration
24 V DCControl voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

LC1D18BD — selected manufacturer specifications
Product referenceLC1D18BD
Range of productTeSys Deca
Product or component typeContactor
Device short nameLC1D
Contactor applicationMotor control Resistive load
Utilisation categoryAC-3 AC-3e AC-1 AC-4
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC
[Ie] rated operational current18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage24 V DC
Motor power kW4 kW at 220/230 V AC 50/60 Hz (AC-3) 7.5 kW at 380/400 V AC 50/60 Hz (AC-3) 9 kW at 415/440 V AC 50/60 Hz (AC-3) 10 kW at 500 V AC 50/60 Hz (AC-3) 10 kW at 660/690 V AC 50/60 Hz (AC-3) 4 kW at 220/230 V AC 50/60 Hz (AC-3e) 7.5 kW at 380/400 V AC 50/60 Hz (AC-3e) 9 kW at 415/440 V AC 50/60 Hz (AC-3e) 10 kW at 500 V AC 50/60 Hz (AC-3e) 10 kW at 660/690 V AC 50/60 Hz (AC-3e) 4 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp1 hp at 115 V AC 50/60 Hz for 1 phase motors 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors 5 hp at 230/240 V AC 50/60 Hz for 3 phases motors 10 hp at 460/480 V AC 50/60 Hz for 3 phases motors 15 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit 32 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 300 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity300 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current145 A 40 °C - 10 s for power circuit 240 A 40 °C - 1 s for power circuit 40 A 40 °C - 10 min for power circuit 84 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1 50 A gG at <= 690 V coordination type 1 for power circuit 35 A gG at <= 690 V coordination type 2 for power circuit
Average impedance2.5 mOhm - Ith 32 A 50 Hz for power circuit
Power dissipation per pole2.5 W AC-1 0.8 W AC-3 0.8 W AC-3e
[Ui] rated insulation voltagePower circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability30 Mcycles
Electrical durability1.65 Mcycles 18 A AC-3 at Ue <= 440 V 1 Mcycles 32 A AC-1 at Ue <= 440 V 1.65 Mcycles 18 A AC-3e at Ue <= 440 V
Control circuit typeDC standard
Coil technologyWith integral suppression device
Control circuit voltage limits0.1...0.25 Uc (-40…70 °C):drop-out DC 0.7...1.25 Uc (-40…60 °C):operational DC 1...1.25 Uc (60…70 °C):operational DC
Inrush power in W5.4 W (at 20 °C)
Hold-in power consumption in W5.4 W at 20 °C
Operating time63 ±15 % ms closing 20 ±20 % ms opening
Time constant28 ms
Maximum operating rate3600 cyc/h at 60 °C
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable end
Tightening torquePower circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency25...400 Hz
Minimum switching voltage17 V for signalling circuit
Minimum switching current5 mA for signalling circuit
Insulation resistance> 10 MOhm for signalling circuit
Non-overlap time1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Mounting supportPlate Rail
StandardsCSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ CSA C22.2 No 60947-4-1
Product certificationsUL CCC CSA Marine UKCA EAC CB Scheme
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C 60…70 °C with derating
Operating altitude0...3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor open (10 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms)
Height77 mm
Width45 mm
Depth95 mm
Net weight0.49 kg

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.