AurFort
Easy TeSys ControlSchneider Electric Easy TeSys contactor 3P(3 NO) - AC-3 - <= 440 V 160A - 220 V AC coil, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACTOR

Easy TeSys contactor 3P(3 NO) - AC-3 - <= 440 V 160A - 220 V AC coil

SKU LC1E160M5

Schneider Electric LC1E160M5 is a contactor in the Easy TeSys Control range. Key specifications include operational current: 160 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; contact configuration: 3 NO; control voltage: 220 V AC 50 Hz.

160 A (at <55 °C) at <= 440 V AC AC-3 for power circuitOperational current
3 NOContact configuration
220 V AC 50 HzControl voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

LC1E160M5 — selected manufacturer specifications
Product referenceLC1E160M5
RangeEasy TeSys
Range of productEasy TeSys Control
Product or component typeContactor
Device short nameLC1E
Contactor applicationMotor control Resistive load
Utilisation categoryAC-3 AC-3e AC-1
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current160 A (at <55 °C) at <= 440 V AC AC-3 for power circuit 100 A (at <55 °C) at <= 440 V AC AC-3e for power circuit 200 A (at <40 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage220 V AC 50 Hz
Motor power kW45 kW at 220/230 V AC 50/60 Hz 75 kW at 380/400 V AC 80 kW at 415/440 V AC 90 kW at 500 V AC 100 kW at 660/690 V AC 100 kW at 660...690 V
Pole contact composition3 NO
[Ith] conventional free air thermal current200 A (at 40 °C) for power circuit
Irms rated making capacity1600 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity1280 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current1400 A 40 °C - 10 s for power circuit
Associated fuse rating315 A gG at <= 690 V coordination type 1 for power circuit 10 A gG at <= 690 V for auxiliary contact circuit conforming to IEC 60947-5-1
Average impedance0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole24 W AC-1 15 W AC-3
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
Mechanical durability4000000 cycles
Electrical durability800000 cycles AC-3 250000 cycles AC-1
Control circuit typeAC at 50 Hz
Control circuit voltage limits0.85...1.1 Uc (-5…55 °C):operational 50 Hz 0.35...0.55 Uc (-5…55 °C):drop-out 50 Hz
Inrush power in VA300 VA 50 Hz cos phi 0.9 (at 20 °C) 300 VA 60 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA22 VA 50 Hz cos phi 0.9 (at 20 °C) 22 VA 60 Hz cos phi 0.9 (at 20 °C)
Heat dissipation3…8 W for control circuit
Operating time20...50 ms on closing 6...20 ms on opening
Maximum operating rate1200 cyc/h 55 °C
Connections - terminalsPower circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 10…120 mm² - cable stiffness: solid without cable end
Tightening torquePower circuit: 12 N.m Control circuit: 1.2 N.m
Auxiliary contact composition1 NO + 1 NC
Minimum switching voltage17 V for auxiliary contact circuit
Minimum switching current5 mA for auxiliary contact circuit
Insulation resistance> 10 MOhm for auxiliary contact circuit
Non-overlap time1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact
Mounting supportPlate DIN rail
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
Product certificationsCB Scheme CCC CE EAC
IP degree of protectionIP2X conforming to IEC 60529
Protective treatmentTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Permissible ambient air temperature around the device-20…70 °C at Uc -60…80 °C storage -5…55 °C operation
Operating altitude3000 m without derating
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Height158 mm
Width120 mm
Depth132 mm
Net weight2.3 kg