AurFort
Easy TeSys ControlSchneider Electric Easy TeSys contactor 3P(3 NO) - AC-3 - <= 440 V 250A - 220 V AC coil, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACTOR

Easy TeSys contactor 3P(3 NO) - AC-3 - <= 440 V 250A - 220 V AC coil

SKU LC1E250M5

Schneider Electric LC1E250M5 is a contactor in the Easy TeSys Control range. Key specifications include operational current: 250 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; contact configuration: 3 NO; control voltage: 220 V AC 50 Hz.

250 A (at <55 °C) at <= 440 V AC AC-3 for power circuitOperational current
3 NOContact configuration
220 V AC 50 HzControl voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

LC1E250M5 — selected manufacturer specifications
Product referenceLC1E250M5
RangeEasy TeSys
Range of productEasy TeSys Control
Product or component typeContactor
Device short nameLC1E
Contactor applicationMotor control Resistive load
Utilisation categoryAC-3 AC-3e AC-1
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current250 A (at <55 °C) at <= 440 V AC AC-3 for power circuit 190 A (at <55 °C) at <= 440 V AC AC-3e for power circuit 300 A (at <40 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage220 V AC 50 Hz
Motor power kW75 kW at 220/230 V AC 50/60 Hz 132 kW at 380/400 V AC 140 kW at 415/440 V AC 160 kW at 500 V AC 160 kW at 660/690 V AC 160 kW at 660...690 V
Pole contact composition3 NO
[Ith] conventional free air thermal current300 A (at 40 °C) for power circuit
Irms rated making capacity2500 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity2000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current1800 A 40 °C - 10 s for power circuit
Associated fuse rating315 A gG at <= 690 V coordination type 1 for power circuit
Average impedance0.32 mOhm - Ith 300 A 50 Hz for power circuit
Power dissipation per pole20 W AC-3 29 W AC-1
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
Mechanical durability5000000 cycles
Electrical durability200000 cycles AC-1 700000 cycles AC-3
Control circuit typeAC at 50 Hz
Control circuit voltage limits0.85...1.1 Uc (-5…55 °C):operational 50 Hz 0.35...0.55 Uc (-5…55 °C):drop-out 50 Hz
Inrush power in VA805 VA 50 Hz cos phi 0.3 (at 20 °C) 970 VA 60 Hz cos phi 0.3 (at 20 °C)
Hold-in power consumption in VA55 VA 50 Hz cos phi 0.3 (at 20 °C) 66 VA 60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation18…24 W for control circuit
Operating time20...35 ms on closing 7...15 ms on opening
Maximum operating rate1200 cyc/h 55 °C
Connections - terminalsPower circuit: cable with lug 1 1…4 mm² - external diameter: 185 mm - cable stiffness: flexible without cable end Power circuit: bars 2 1…4 mm² - cable stiffness: flexible without cable end - busbar cross section: 32 x 4 mm Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - external diameter: 185 mm - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end - busbar cross section: 32 x 4 mm
Tightening torqueControl circuit: 1.2 N.m Power circuit: 35 N.m
Auxiliary contact compositionWithout
Mounting supportPlate
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 GB/T 14048.1 GB/T 14048.4
Product certificationsCB Scheme CCC CE EAC
IP degree of protectionIP00 conforming to IEC 60529
Permissible ambient air temperature around the device-20…70 °C at Uc -60…80 °C storage -5…55 °C operation
Operating altitude3000 m without derating
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Height197 mm
Width168.5 mm
Depth181 mm
Net weight4.7 kg

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.