AurFort
Easy TeSys ControlSchneider Electric Contactor,Easy TeSys Control,LC1E,4P(2NO+2NC),AC-1 100A,220V, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACTOR

Contactor,Easy TeSys Control,LC1E,4P(2NO+2NC),AC-1 100A,220V

SKU LC1E80008M7

Schneider Electric LC1E80008M7 is a contactor in the Easy TeSys Control range. Key specifications include operational current: 100 A (at <55 °C) at <= 440 V AC AC-1 for power circuit; contact configuration: 2 NO + 2 NC; control voltage: 220 V AC 50/60 Hz.

100 A (at <55 °C) at <= 440 V AC AC-1 for power circuitOperational current
2 NO + 2 NCContact configuration
220 V AC 50/60 HzControl voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

LC1E80008M7 — selected manufacturer specifications
Product referenceLC1E80008M7
RangeEasy TeSys
Range of productEasy TeSys Control
Product or component typeContactor
Device short nameLC1E
Contactor applicationResistive load
Utilisation categoryAC-1
Poles description4P
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Ie] rated operational current100 A (at <55 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage220 V AC 50/60 Hz
Pole contact composition2 NO + 2 NC
[Ith] conventional free air thermal current100 A (at 55 °C) for power circuit
Irms rated making capacity800 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Rated breaking capacity640 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current640 A 40 °C - 10 s for power circuit 320 A 40 °C - 60 s for power circuit 135 A 40 °C - 600 s for power circuit
Associated fuse rating160 A gG at <= 690 V coordination type 1 for power circuit
Average impedance0.8 mOhm - Ith 100 A 50 Hz for power circuit
Power dissipation per pole5.1 W AC-3 9.7 W AC-1
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Mechanical durability3000000 cycles
Electrical durability350000 cycles AC-1 900000 cycles AC-3
Control circuit typeAC at 50/60 Hz
Control circuit voltage limits0.85...1.1 Uc (-5…55 °C):operational 50/60 Hz 0.3...0.6 Uc (-5…55 °C):drop-out 50/60 Hz
Inrush power in VA200 VA 50 Hz cos phi 0.75 (at 20 °C) 220 VA 60 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA22 VA 60 Hz cos phi 0.3 (at 20 °C) 20 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation6…10 W for control circuit
Operating time20...35 ms on closing 6...30 ms on opening
Maximum operating rate1200 cyc/h 60 °C
Connections - terminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 4…50 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 4…16 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 4…50 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 4…50 mm² - cable stiffness: solid without cable end
Tightening torqueControl circuit: 1.2 N.m Power circuit: 12 N.m
Auxiliary contact compositionWithout
Mounting supportPlate DIN rail
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 GB/T 14048.1 GB/T 14048.4
Product certificationsCB Scheme CCC CE EAC
IP degree of protectionIP2X conforming to IEC 60529
Protective treatmentTH (pollution degree 3) conforming to IEC 60068-2-30
Permissible ambient air temperature around the device-20…70 °C at Uc -60…80 °C storage -5…55 °C operation
Operating altitude3000 m without derating
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Height127 mm
Width95 mm
Depth120 mm
Net weight1.6 kg

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.