AurFort
TeSys GigaSchneider Electric High power contactor, TeSys Giga, 4 pole (4NO), AC-1 <=440V 250A, standard version, 100…250V wide band AC/DC coil, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CONTACTOR

High power contactor, TeSys Giga, 4 pole (4NO), AC-1 <=440V 250A, standard version, 100…250V wide band AC/DC coil

SKU LC1G1154KUEN

Schneider Electric LC1G1154KUEN is a contactor in the TeSys Giga range. Key specifications include operational current: 115 A (at <60 °C) at <= 440 V AC-3; contact configuration: 4 NO; control voltage: 100...250 V AC 50/60 Hz.

115 A (at <60 °C) at <= 440 V AC-3Operational current
4 NOContact configuration
100...250 V AC 50/60 HzControl voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

LC1G1154KUEN — selected manufacturer specifications
Product referenceLC1G1154KUEN
RangeTeSys
Range of productTeSys Giga
Product or component typeContactor
Device short nameLC1G
Contactor applicationPower switching
Utilisation categoryAC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5
Poles description4P
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current115 A (at <60 °C) at <= 440 V AC-3 250 A (at <40 °C) at <= 1000 V AC-1
[Uc] control circuit voltage100...250 V AC 50/60 Hz 100...250 V DC
Control circuit voltage limitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C) Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current250 A (at 40 °C)
Rated breaking capacity1040 A at 440 V
[Icw] rated short-time withstand current1.1 kA - 10 s 0.64 kA - 30 s 0.52 kA - 1 min 0.4 kA - 3 min 0.32 kA - 10 min
Associated fuse rating125 A aM at <= 440 V for motor 125 A aM at <= 690 V for motor 315 A gG at <= 690 V 300 A UL Type J at <= 600 V
Average impedance0.00018 Ohm
[Ui] rated insulation voltage1000 V
Power dissipation per pole10 W AC-1 - Ith 250 A 3 W AC-3 - Ith 115 A
Compatibility codeLC1G
Pole contact composition4 NO
Auxiliary contact composition1 NO + 1 NC
Irms rated making capacity1560 A at 440 V
Coil technologyBuilt-in bidirectional peak limiting
Safety reliability levelB10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability8 Mcycles
inrush power in VA (50/60 Hz, AC)540 VA
inrush power in W (DC)380 W
hold-in power consumption in VA (50/60 Hz, AC)12.4 VA
hold-in power consumption in W (DC)7.8 W
Operating time40...70 ms closing 15...50 ms opening
Maximum operating rate600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1
Connections - terminalsPower circuit: bar 2 - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 185 mm² Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5…1.0 mm² with cable end Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end
Connection pitch35 mm
Mounting supportPlate
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
Product certificationsCB Scheme CCC cULus EAC CE UKCA EU-RO-MR by DNV-GL
Tightening torque18 N.m
Height193 mm
Width143 mm
Depth193 mm
Net weight4.4 kg
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-60…80 °C
Mechanical robustnessVibrations 5…300 Hz 2 gn contactor open Vibrations 5…300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
ColourDark grey
Protective treatmentTH
Permissible ambient air temperature around the device-40…70 °C at Uc

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.