AurFort
TeSys LRDSchneider Electric TeSys LRD - electronic thermal overload relay - 3P - 0.4...2 A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

ELECTRONIC THERMAL OVERLOAD RELAY

TeSys LRD - electronic thermal overload relay - 3P - 0.4...2 A

SKU LR9D02

Schneider Electric LR9D02 is a electronic thermal overload relay in the TeSys LRD range. Key specifications include current setting range: 0.4…2 A; thermal overload class: Class 5…30; operational voltage: 690 V for power circuit.

0.4…2 ACurrent setting range
Class 5…30Thermal overload class
690 V for power circuitOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 06, 2026.

LR9D02 — selected manufacturer specifications
Product referenceLR9D02
RangeTeSys
Product nameTeSys LRD
Device short nameLR9D
Product or component typeElectronic thermal overload relay
Relay applicationMotor protection
Product compatibilityLC1D25 LC1D09 LC1D32 LC1D38 LC1D18 LC1D12
Thermal overload classClass 5…30
Thermal protection adjustment range0.4…2 A
Power consumption in W300 mW
Mounting supportUnder contactor Plate, with specific accessories Rail, with specific accessories
[Ue] rated operational voltage690 V for power circuit 660 V for signalling circuit
[Ui] rated insulation voltagePower circuit: 1000 V Signalling circuit: 690 V
Tripping threshold1.25 In conforming to IEC 60947-4-1
Control typeRed push-button: stop and manual reset White 2 microswitches: adjustable trip class Red knob: automatic reset White dial: full-load current adjustment
Time range1.5...4 min - automatic reset time
[Ith] conventional free air thermal current5 A for signalling circuit
Associated fuse rating5 A gG for signalling circuit 5 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
Phase failure sensitivityPhase difference > 40% 3 s conforming to IEC 60947-4-1
Electromagnetic compatibilitySurge withstand: 2 kV common mode conforming to IEC 61000-4-5 Resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2 Immunity to radiated radio-electrical interference: 10 V/m conforming to IEC 61000-4-3 Immunity to fast transients: 2 kV conforming to IEC 61000-4-4
Connections - terminalsControl circuit: screw clamp terminals 1 cable 2.5 mm² - cable stiffness: solid or flexible - without cable end Power circuit: screw clamp terminals 1 cable 16 mm² - cable stiffness: solid or flexible - without cable end
Tightening torqueControl circuit: 0.8 N.m on screw clamp terminals Power circuit: 3.1 N.m on screw clamp terminals
Height72.5 mm
Width45 mm
Depth79.9 mm
Net weight0.18 kg
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5
Product certificationsIECEE CB Scheme UL CSA CCC
IP degree of protectionIP20 front face conforming to IEC 60529
Ambient air temperature for operation-25…70 °C conforming to IEC 60255-8
Ambient air temperature for storage-55…80 °C
Operating altitude2000 m without derating
Mechanical robustnessVibrations 10...150 Hz: 6 Gn conforming to IEC 60068-2-6 Shocks 11 ms: 15 gn conforming to IEC 60068-2-7
Dielectric strength6 kV 50 Hz conforming to IEC 60255-5