Schneider Electric catalog image for this SKU; may represent the product family.
ELECTRONIC THERMAL OVERLOAD RELAY
TeSys LRD thermal overload relays - 60...100 A - class 10
SKU LR9D5367Schneider Electric LR9D5367 is a electronic thermal overload relay in the TeSys LRD range. Key specifications include current setting range: 60…100 A; thermal overload class: Class 10 conforming to IEC 60947-4-1; auxiliary contacts: 1 NO + 1 NC.
60…100 ACurrent setting range
Class 10 conforming to IEC 60947-4-1Thermal overload class
1 NO + 1 NCAuxiliary contacts
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 18, 2026.
| Product reference | LR9D5367 |
|---|---|
| Range | TeSys |
| Product name | TeSys LRD TeSys Deca |
| Product or component type | Electronic thermal overload relay |
| Device short name | LR9D |
| Relay application | Motor protection |
| Product compatibility | LC1D115 LC1D150 NSX circuit breaker |
| Network type | AC |
| Thermal overload class | Class 10 conforming to IEC 60947-4-1 |
| Signalling function | Alarm |
| Thermal protection adjustment range | 60…100 A |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL |
| Network frequency | 50...60 Hz |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 17…32 V |
| Mounting support | Under contactor Rail |
| Tripping threshold | 1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1 1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| [Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
| Associated fuse rating | 4 A gG for signalling circuit 4 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
| Phase failure sensitivity | Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1 |
| Control type | Red push-button: stop Blue push-button: reset |
| Temperature compensation | -20…60 °C |
| Switching capacity in mA | 0...150 mA |
| Maximum voltage drop | <2.5 V closed state |
| Connections - terminals | Power circuit: bars Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end |
| Tightening torque | Alarm circuit: 0.45 N.m - on screw clamp terminals Power circuit: 18 N.m - on bars M8 Control circuit: 1.2 N.m - on screw clamp terminals |
| Height | 118 mm |
| Width | 115 mm |
| Depth | 125 mm |
| Net weight | 0.885 kg |
| Climatic withstand | conforming to IACS E10 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60…70 °C |
| Operating altitude | <= 2000 m without derating |
| Mechanical robustness | Vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7 |
| Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5 |
| Product certifications | UL CSA CCC UKCA |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.