AurFort
TeSys LRGSchneider Electric Electronic thermal overload relay,TeSys Giga,28-115 A,class 5E-30E,push-in control connection, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

ELECTRONIC THERMAL OVERLOAD RELAY

Electronic thermal overload relay,TeSys Giga,28-115 A,class 5E-30E,push-in control connection

SKU LR9G115

Schneider Electric LR9G115 is a electronic thermal overload relay in the TeSys LRG range. Key specifications include current setting range: 28…115 A; thermal overload class: Class 5E...30E conforming to IEC 60947-4-1; operational voltage: 1000 V AC 50/60 Hz.

28…115 ACurrent setting range
Class 5E...30E conforming to IEC 60947-4-1Thermal overload class
1000 V AC 50/60 HzOperational voltage
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

LR9G115 — selected manufacturer specifications
Product referenceLR9G115
RangeTeSys
Product nameTeSys LRG
Product or component typeElectronic thermal overload relay
Device short nameLR9G
Relay applicationMotor protection
Network typeAC
Thermal overload classClass 5E...30E conforming to IEC 60947-4-1
Thermal protection adjustment range28…115 A
Network frequency30...60 Hz 100 Hz
Overvoltage categoryIII
Tripping threshold1.125 +/- 0.07 In conforming to IEC 60947-4-1
Protection typeGround fault protection - tripping time adjustment: 0…1 s - for alarm circuit conforming to IEC 60947-4-1 Ground fault protection - tripping time adjustment: 0…1 s - for alarm circuit conforming to UL 60947-4-1 Phase loss - tripping time adjustment: 0…4 s - for alarm circuit Phase imbalance - tripping time adjustment: 0…5 s - for alarm circuit conforming to IEC 60947-4-1 Phase imbalance - tripping time adjustment: 0…5 s - for alarm circuit conforming to UL 60947-4-1
Local signallingLED Trip indicator
Contacts type and composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A
[Uc] control circuit voltage24...500 V AC 50/60 Hz 24...250 V DC
[Ue] rated operational voltage1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
ResetAutomatic reset Manual
Mechanical durability7000 cycles
Surge withstand4 kV
Electromagnetic compatibilityEMC immunity conforming to IEC 60947-4-1 Emission tests criteria A conforming to IEC 60947-4-1 Immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to SEMI F47
Connections - terminalsPower circuit: bar - busbar cross section: 25 x 6 mm Power circuit: lugs-ring terminals 1 185 mm² Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end Control circuit: push-in 2 0.5…1.0 mm² with cable end
Tightening torque18 N.m
Mounting supportDirect on contactor Plate
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ UL 60335-1
Product certificationsCB Scheme CCC cULus UKCA ATEX EU-RO-MR by DNV-GL EAC
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Protective treatmentTH
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-60…80 °C
Permissible ambient air temperature around the device-40…60 °C at Uc
Adjustment of dial setting-25…60 °C
Mechanical robustnessVibrations 5…300 Hz 6 gn contactor open Shocks 15 gn 11 ms contactor closed
Height107 mm
Width105 mm
Depth126 mm
Net weight0.8 kg
ColourDark grey

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.