AurFort
TeSys LRDSchneider Electric TeSys LRD thermal overload relays - 0.25...0.4 A - class 10A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

DIFFERENTIAL THERMAL OVERLOAD RELAY

TeSys LRD thermal overload relays - 0.25...0.4 A - class 10A

SKU LRD03

Schneider Electric LRD03 is a differential thermal overload relay in the TeSys LRD range. Key specifications include current setting range: 0.25…0.4 A; thermal overload class: Class 10A conforming to IEC 60947-4-1; auxiliary contacts: 1 NO + 1 NC.

0.25…0.4 ACurrent setting range
Class 10A conforming to IEC 60947-4-1Thermal overload class
1 NO + 1 NCAuxiliary contacts
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

LRD03 — selected manufacturer specifications
Product referenceLRD03
RangeTeSys TeSys Deca
Product nameTeSys LRD TeSys Deca
Product or component typeDifferential thermal overload relay
Device short nameLRD
Relay applicationMotor protection
Product compatibilityLC1D25 LC1D18 LC1D38 LC1D12 LC1D32 LC1D09
Network typeAC DC
Thermal overload classClass 10A conforming to IEC 60947-4-1
Thermal protection adjustment range0.25…0.4 A
[Ui] rated insulation voltagePower circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1
Network frequency0...400 Hz
Mounting supportPlate, with specific accessories Rail, with specific accessories Under contactor
Tripping threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary contact composition1 NO + 1 NC
[Ith] conventional free air thermal current5 A for signalling circuit
Permissible current3 A at 120 V AC-15 for signalling circuit 0.22 A at 125 V DC-13 for signalling circuit
[Ue] rated operational voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating4 A gG for signalling circuit 4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage6 kV
Phase failure sensitivityTripping current 130 % of Ir on two phase, the last one at 0
Control typeRed push-button: stop Blue push-button: reset
Temperature compensation-20…60 °C
Connections - terminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end
Tightening torqueControl circuit: 1.7 N.m - on screw clamp terminals Power circuit: 1.7 N.m - on screw clamp terminals
Height66 mm
Width45 mm
Depth70 mm
Net weight0.124 kg
Climatic withstandconforming to IACS E10
IP degree of protectionIP20 conforming to IEC 60529
Ambient air temperature for operation-20…60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature for storage-60…70 °C
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations: 6 Gn conforming to IEC 60068-2-6 Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
Dielectric strength1.89 kV at 50 Hz conforming to IEC 60947-1
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4 GB/T 14048.5 EN 50495
Product certificationsIEC UL CSA CCC EAC BV RINA DNV-GL LROS (Lloyds register of shipping) ATEX INERIS UKCA