AurFort
Harmony Timer RelaysSchneider Electric Star-Delta Timing Relay - 0.05s…300s - 24V DC / 24…240V AC - 1C/O, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

MODULAR TIMING RELAY

Star-Delta Timing Relay - 0.05s…300s - 24V DC / 24…240V AC - 1C/O

SKU RE22R1QCMU

Schneider Electric RE22R1QCMU is a modular timing relay in the Harmony Timer Relays range. Key specifications include mounting support: 35 mm DIN rail conforming to IEC 60715; ip protection: IP40 housing: conforming to IEC 60529; net weight: 0.08 kg.

35 mm DIN rail conforming to IEC 60715Mounting support
IP40 housing: conforming to IEC 60529IP protection
0.08 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

RE22R1QCMU — selected manufacturer specifications
Product referenceRE22R1QCMU
Range of productHarmony Timer Relays
Discrete output typeRelay
Product or component typeModular timing relay
Device short nameRE22
nominal output current8 A
Contacts type and composition1 C/O timed contact, cadmium free
Time delay typeStar-delta - Qc-Star-delta relay (1 CO output)
Time delay range10...100 s 3...30 s 0.1...1 s 0.3...3 s 0.05...0.5 s 1...10 s 30...300 s
Control typeWith test button
[Us] rated supply voltage24 V DC 24...240 V AC 50/60 Hz
Release input voltage<= 2.4 V
Voltage range0.85...1.1 Us
Supply frequency50...60 Hz +/- 5 %
Connections - terminalsScrew terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end
Tightening torque0.6…1 N.m conforming to IEC 60947-1
Housing materialPolycarbonate
Repeat accuracy+/- 0.5 % conforming to IEC 61812-1
Temperature drift+/- 0.05 %/°C
Voltage drift+/- 0.2 %/V
Setting accuracy of time delay+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Insulation resistance100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time120 ms on de-energisation
Immunity to microbreaks10 ms
Power consumption in VA35 VA at 240 V AC
Power consumption in W0.6 W at 24 V DC
Switching capacity in VA2000 VA
Minimum switching current10 mA at 5 V DC
Maximum switching current8 A
Maximum switching voltage250 V AC
Electrical durability100000 cycles, 8 A at 250 V, AC-1 100000 cycles, 2 A at 24 V, DC-1
Mechanical durability10000000 cycles
Rated impulse withstand voltage5 kV for 1.2…50 µs conforming to IEC 60664-1
Power on delay100 ms
Creepage distance4 kV/3 conforming to IEC 60664-1
Overvoltage categoryIII conforming to IEC 60664-1
Safety reliability dataMTTFd = 285.3 years B10d = 270000
Mounting positionAny position
Mounting support35 mm DIN rail conforming to IEC 60715
Status LEDLED backlight green (steady) for dial pointer indication LED yellow (steady) for output relay energised LED yellow (fast flashing) for timing in progress and output relay de-energised LED yellow (slow flashing) for timing in progress and output relay energised
Function availableQc-Star-delta relay (1 CO output)-1 C/O
Width22.5 mm
Net weight0.08 kg
Number of functions1
Dielectric strength2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1
StandardsUL 508 IEC 61812-1
Directives2004/108/EC - electromagnetic compatibility 2006/95/EC - low voltage directive
Product certificationsGL CE CCC EAC UL CSA RCM
Ambient air temperature for operation-20…60 °C
Ambient air temperature for storage-40…70 °C
IP degree of protectionIP40 housing: conforming to IEC 60529 IP50 front face: conforming to IEC 60529 IP20 terminals: conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Vibration resistance20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock resistance15 gn not operating for 11 ms conforming to IEC 60068-2-27 5 gn in operation for 11 ms conforming to IEC 60068-2-27
Relative humidity95 % at 25…55 °C
Electromagnetic compatibilityFast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4 Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3 Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6 Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4 Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11 Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.