Schneider Electric catalog image for this SKU; may represent the product family.
CURRENT CONTROL RELAY
Current control relay 0.15A…15A, 2 C/O
SKU RM35JA32MRSchneider Electric RM35JA32MR is a current control relay in the Harmony Control Relays range. Key specifications include mounting support: 35 mm DIN rail conforming to IEC 60715; ip protection: IP20 (terminals) conforming to IEC 60529; net weight: 0.12 kg.
35 mm DIN rail conforming to IEC 60715Mounting support
IP20 (terminals) conforming to IEC 60529IP protection
0.12 kgNet weight
PRODUCT DATA
Technical specifications
Source: Schneider Electric product catalog.
Verified September 18, 2026.
| Product reference | RM35JA32MR |
|---|---|
| Range of product | Harmony Control Relays |
| Relay type | Current control relay |
| Product or component type | Current control relay |
| Relay name | RM35JA |
| Relay monitored parameters | Overcurrent or undercurrent in window mode Overcurrent or undercurrent detection |
| Control type | With test button |
| Contacts type and composition | 2 C/O |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 20.4…264 V AC/DC |
| Maximum power consumption in VA | 3.5 VA |
| Maximum power consumption in W | 1.5 W DC |
| Measurement range | 150 mA...15 A AC/DC |
| Maximum measuring cycle | 100 ms measurement cycle as true rms value |
| Hysteresis | 5…50 % adjustable of threshold setting 3 % fixed of full scale for window mode |
| Setting accuracy of the switching threshold | +/- 10 % of the full scale |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit +/- 2 % for time delay |
| Measurement error | < 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation |
| Time delay type | Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms at maximum voltage |
| Response time | <= 500 ms (on crossing the threshold) |
| Power on Delay | 300 ms |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 2000 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 8 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| operating voltage tolerance | - 15 % + 10 % Un |
| Resistance across terminals | 0.005 Ohm at E3-M terminals 0.015 Ohm at E2-M terminals 0.05 Ohm at E1-M terminals |
| Threshold setting | 10...100 % |
| Insulation | Between supply and measurement |
| Contacts material | Cadmium free |
| Electromagnetic compatibility | Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for industrial environments conforming to IEC 61000-6-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to IEC 61000-6-3 |
| Standards | IEC 60255-1 |
| Product certifications | CE GL CCC EAC RCM UL CSA |
| Ambient air temperature for storage | -40…70 °C -40…70 °C |
| Ambient air temperature for operation | -20…50 °C at 60 Hz -20…60 °C at 50 Hz |
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 IP30 (housing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |
| Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (yellow) for relay ON LED (green) for power ON |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 296.8 years B10d = 270000 |
| Height | 90 mm 88.9 mm |
| Width | 35 mm 35.6 mm |
| Depth | 73 mm 73.7 mm |
| Net weight | 0.12 kg 0.12 kg |
| Environmental characteristic | 3K3 C |
For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.