AurFort
Harmony Control RelaysSchneider Electric Current control relay 0.15A…15A, 2 C/O, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

CURRENT CONTROL RELAY

Current control relay 0.15A…15A, 2 C/O

SKU RM35JA32MR

Schneider Electric RM35JA32MR is a current control relay in the Harmony Control Relays range. Key specifications include mounting support: 35 mm DIN rail conforming to IEC 60715; ip protection: IP20 (terminals) conforming to IEC 60529; net weight: 0.12 kg.

35 mm DIN rail conforming to IEC 60715Mounting support
IP20 (terminals) conforming to IEC 60529IP protection
0.12 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

RM35JA32MR — selected manufacturer specifications
Product referenceRM35JA32MR
Range of productHarmony Control Relays
Relay typeCurrent control relay
Product or component typeCurrent control relay
Relay nameRM35JA
Relay monitored parametersOvercurrent or undercurrent in window mode Overcurrent or undercurrent detection
Control typeWith test button
Contacts type and composition2 C/O
[Us] rated supply voltage24...240 V AC/DC 50/60 Hz, non self-powered
Supply voltage limits20.4…264 V AC/DC
Maximum power consumption in VA3.5 VA
Maximum power consumption in W1.5 W DC
Measurement range150 mA...15 A AC/DC
Maximum measuring cycle100 ms measurement cycle as true rms value
Hysteresis5…50 % adjustable of threshold setting 3 % fixed of full scale for window mode
Setting accuracy of the switching threshold+/- 10 % of the full scale
Repeat accuracy+/- 0.5 % for input and measurement circuit +/- 2 % for time delay
Measurement error< 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
Time delay typeAdjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault
Setting accuracy of time delay10 %
Reset time1500 ms at maximum voltage
Response time<= 500 ms (on crossing the threshold)
Power on Delay300 ms
Output contacts2 C/O
nominal output current8 A
Maximum switching voltage250 V AC
Switching capacity in VA2000 VA
Minimum switching current10 mA at 5 V DC
Maximum switching current8 A AC
Electrical durability100000 cycles
Mechanical durability10000000 cycles
operating voltage tolerance- 15 % + 10 % Un
Resistance across terminals0.005 Ohm at E3-M terminals 0.015 Ohm at E2-M terminals 0.05 Ohm at E1-M terminals
Threshold setting10...100 %
InsulationBetween supply and measurement
Contacts materialCadmium free
Electromagnetic compatibilityImmunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for industrial environments conforming to IEC 61000-6-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to IEC 61000-6-3
StandardsIEC 60255-1
Product certificationsCE GL CCC EAC RCM UL CSA
Ambient air temperature for storage-40…70 °C -40…70 °C
Ambient air temperature for operation-20…50 °C at 60 Hz -20…60 °C at 50 Hz
Relative humidity93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protectionIP20 (terminals) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 IP30 (housing) conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Overvoltage categoryIII conforming to IEC 60664-1
Dielectric test voltage2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Insulation resistance> 100 MOhm at 500 V DC conforming to IEC 60255-27
Connections - terminalsScrew terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end
Tightening torque0.6…1 N.m conforming to IEC 60947-1
Housing materialPolycarbonate
Local signallingLED (yellow) for relay ON LED (green) for power ON
Mounting support35 mm DIN rail conforming to IEC 60715
Reliability dataMTTFd = 296.8 years B10d = 270000
Height90 mm 88.9 mm
Width35 mm 35.6 mm
Depth73 mm 73.7 mm
Net weight0.12 kg 0.12 kg
Environmental characteristic3K3 C

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.