AurFort
Harmony Electromechanical RelaysSchneider Electric universal plug-in relay - HARMONY RUM - 3 C/O - 24 V DC - 10 A, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

PLUG-IN RELAY

universal plug-in relay - HARMONY RUM - 3 C/O - 24 V DC - 10 A

SKU RUMC31BD

Schneider Electric RUMC31BD is a plug-in relay in the Harmony Electromechanical Relays range. Key specifications include ip protection: IP40; control voltage: 24 V DC; net weight: 0.086 kg.

IP40IP protection
24 V DCControl voltage
0.086 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

RUMC31BD — selected manufacturer specifications
Product referenceRUMC31BD
Range of productHarmony Electromechanical Relays
Series nameRUM series
Product or component typePlug-in relay
Relay typeUniversal relay
Contacts type and composition3 C/O
status LEDWithout
Control typeLockable test button
[Uc] control circuit voltage24 V DC
[Ithe] conventional enclosed thermal current10 A at -40…55 °C
[Uimp] rated impulse withstand voltage4 kV (1.2/50 µs)
Minimum switching capacity170 mW at 10 mA, 17 V
Electrical durability100000 cycles for resistive load
Operating time20 ms at nominal voltage
Rated operational voltage limits19.2...26.4 V DC
[Ui] rated insulation voltage250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL
Reset time20 ms at nominal voltage
Maximum switching voltage250 V conforming to IEC
Drop-out voltage threshold>= 0.1 Uc DC
[Ie] rated operational current10 A at 277 V AC conforming to UL 10 A at 30 V DC conforming to UL 10 A at 277 V AC (same polarity) conforming to CSA 10 A at 30 V DC conforming to CSA 5 A at 250 V AC (NC) conforming to IEC 5 A at 28 V DC (NC) conforming to IEC 10 A at 250 V AC (NO) conforming to IEC 10 A at 28 V DC (NO) conforming to IEC
Average resistance470 Ohm at 20 °C +/- 15 %
Maximum switching capacity2500 VA/280 W
Mechanical durability5000000 cycles
Safety reliability dataB10d = 100000
Operating rate<= 18000 cycles/hour no-load <= 1200 cycles/hour under load
Utilisation coefficient20 %
Compatibility codeRUM
Dielectric strength1500 V AC between contacts with micro disconnection 2500 V AC between coil and contact with reinforced 2000 V AC between poles with basic
Protection categoryRT I
Pollution degree2
Operating positionAny position
Test levelsLevel A group mounting
Device presentationComplete product
Contacts materialAgNi
Shape of pinCylindrical
Net weight0.086 kg
Average coil consumption1.4 W
Load current10 A at 250 V AC 10 A at 28 V DC
Ambient air temperature for operation-40…55 °C
IP degree of protectionIP40
StandardsIEC 61810-1 CSA C22.2 No 14 UL 508
Product certificationsEAC UL CSA
Ambient air temperature for storage-40…85 °C
Vibration resistance3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 4 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Shock resistance10 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 10 gn (duration = 11 ms) for not operating conforming to IEC 60068-2-27