AurFort
Harmony Electromechanical RelaysSchneider Electric Harmony, Miniature plug-in relay, 10 A, 3 CO, with lockable test button, 24 V DC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

PLUG-IN RELAY

Harmony, Miniature plug-in relay, 10 A, 3 CO, with lockable test button, 24 V DC

SKU RXM3AB1BD

Schneider Electric RXM3AB1BD is a plug-in relay in the Harmony Electromechanical Relays range. Key specifications include ip protection: IP40 conforming to IEC 60529; control voltage: 24 V DC; net weight: 0.037 kg.

IP40 conforming to IEC 60529IP protection
24 V DCControl voltage
0.037 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 18, 2026.

RXM3AB1BD — selected manufacturer specifications
Product referenceRXM3AB1BD
Range of productHarmony Electromechanical Relays
Series nameRXM series
Product or component typePlug-in relay
Relay typeMiniature relay
Contacts type and composition3 C/O
status LEDWithout
Control typeLockable test button
[Uc] control circuit voltage24 V DC
[Ithe] conventional enclosed thermal current10 A
Continuous output current6.7 A
[Uimp] rated impulse withstand voltage4 kV during 1.2/50 µs
[Ie] rated operational current10 A at 28 V (DC) NO conforming to IEC 10 A at 250 V (AC) NO conforming to IEC 5 A at 28 V (DC) NC conforming to IEC 5 A at 250 V (AC) NC conforming to IEC 10 A at 30 V (DC) conforming to UL 10 A at 277 V (AC) conforming to UL
Minimum switching capacity170 mW at 10 mA, 17 V
Electrical durability100000 cycles for resistive load
Rated operational voltage limits19.2...26.4 V DC
[Ui] rated insulation voltage250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL
Maximum switching voltage250 V conforming to IEC
Drop-out voltage threshold>= 0.1 Uc
Load current10 A at 250 V AC 10 A at 28 V DC
Operating time20 ms
Maximum switching capacity2500 VA/280 W
Average resistance650 Ohm at 20 °C +/- 10 %
Average coil consumption0.9 W
Mechanical durability10000000 cycles
Safety reliability dataB10d = 100000
Operating rate<= 1200 cycles/hour under load <= 18000 cycles/hour no-load
Utilisation coefficient20 %
CAD overall height82.8 mm
CAD overall depth80.35 mm
Reset time20 ms
Dielectric strength1300 V AC between contacts with micro disconnection 2000 V AC between coil and contact 2000 V AC between poles
Compatibility codeRXM
Protection categoryRT I
Pollution degree2
Operating positionAny position
Test levelsLevel A group mounting
Device presentationComplete product
Contacts materialAgNi
Shape of pinFlat (faston type)
Net weight0.037 kg
Ambient air temperature for operation-40…55 °C
IP degree of protectionIP40 conforming to IEC 60529
StandardsIEC 61810-1 CSA C22.2 No 14 UL 508
Product certificationsUL Lloyd's CE CSA GOST IECEE CB Scheme
Ambient air temperature for storage-40…85 °C
Vibration resistance3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Shock resistance10 gn for in operation 30 gn for not operating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.