AurFort
Harmony Electromechanical RelaysSchneider Electric Miniature plug-in relay, 6 A, 4 CO, 120 V AC, manufacturer catalog image

Schneider Electric catalog image for this SKU; may represent the product family.

PLUG-IN RELAY

Miniature plug-in relay, 6 A, 4 CO, 120 V AC

SKU RXM4AB1F7

Schneider Electric RXM4AB1F7 is a plug-in relay in the Harmony Electromechanical Relays range. Key specifications include ip protection: IP40 conforming to IEC 60529; control voltage: 120 V AC 50/60 Hz; net weight: 0.037 kg.

IP40 conforming to IEC 60529IP protection
120 V AC 50/60 HzControl voltage
0.037 kgNet weight
PRODUCT DATA

Technical specifications

Source: Schneider Electric product catalog.
Verified September 17, 2026.

RXM4AB1F7 — selected manufacturer specifications
Product referenceRXM4AB1F7
Range of productHarmony Electromechanical Relays
Series nameRXM series
Product or component typePlug-in relay
Relay typeMiniature relay
Contacts type and composition4 C/O
status LEDWithout
Control typeLockable test button
[Uc] control circuit voltage120 V AC 50/60 Hz
[Ithe] conventional enclosed thermal current6 A
Continuous output current5 A
[Uimp] rated impulse withstand voltage2.5 kV during 1.2/50 µs
[Ie] rated operational current3 A at 28 V (DC) NC conforming to IEC 3 A at 250 V (AC) NC conforming to IEC 6 A at 28 V (DC) NO conforming to IEC 6 A at 250 V (AC) NO conforming to IEC 6 A at 277 V (AC) conforming to UL 8 A at 30 V (DC) conforming to UL
Minimum switching capacity170 mW at 10 mA, 17 V
Electrical durability100000 cycles for resistive load
Average coil consumption in VA1.2 at 60 Hz
Rated operational voltage limits96...132 V AC
[Ui] rated insulation voltage250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL
Average consumption1.2 VA at 60 Hz
Maximum switching voltage250 V conforming to IEC
Drop-out voltage threshold>= 0.15 Uc
Load current6 A at 250 V AC 6 A at 28 V DC
Operating time20 ms
Maximum switching capacity1500 VA/168 W
Average resistance4430 Ohm at 20 °C +/- 15 %
Mechanical durability10000000 cycles
Safety reliability dataB10d = 100000
Operating rate<= 1200 cycles/hour under load <= 18000 cycles/hour no-load
Utilisation coefficient20 %
CAD overall height79 mm
CAD overall depth78.45 mm
Reset time20 ms
Dielectric strength1300 V AC between contacts with micro disconnection 2000 V AC between coil and contact with basic insulation 2000 V AC between poles with basic insulation
Compatibility codeRXM
Protection categoryRT I
Pollution degree2
Operating positionAny position
Test levelsLevel A group mounting
Device presentationComplete product
Contacts materialAgNi
Shape of pinFlat (faston type)
Net weight0.037 kg
Ambient air temperature for operation-40…55 °C
IP degree of protectionIP40 conforming to IEC 60529
StandardsUL 508 IEC 61810-1 CSA C22.2 No 14
Product certificationsUL Lloyd's CE CSA GOST IECEE CB Scheme
Ambient air temperature for storage-40…85 °C
Vibration resistance3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
Shock resistance10 gn for in operation 30 gn for not operating

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official Schneider Electric reference ↗.