AurFort
ABBEK1000-40-11ABB EK1000-40-11 220-230V 50Hz / 240V 60Hz, manufacturer catalog image

ABB catalog image for this SKU; may represent the product family.

POWER CONTACTOR, AC SWITCHING

EK1000-40-11 220-230V 50Hz / 240V 60Hz

SKU SK827044-AL

ABB EK1000-40-11 220-230V 50Hz / 240V 60Hz: Power contactor, AC switching. Pole configuration: 4P.

4PPoles
EK1000-40-11Product range
Power contactor, AC switchingProduct type
PRODUCT DATA

Technical specifications

Source: ABB English regional product catalog.
Verified September 09, 2026.

SK827044-AL — selected manufacturer specifications
Product IDSK827044-AL
Catalog DescriptionEK1000-40-11 220-230V 50Hz / 240V 60Hz Contactor
Country of OriginIndia
Made To OrderNo
Warranty ReturnProduct under warranty must be returned
Product Sales StatusActive
Quote OnlyNo
Stocked At WarehousesINABB015EXPU
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Data Sheet, Technical Information1SBC100214C0202
Instructions and Manuals5309660-30
Product Net Width270 mm
Product Net Depth / Length225.5 mm
Product Net Height272 mm
Product Net Weight15.8 kg
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles4P
Rated Operational VoltageMain Circuit 1000 V
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1000 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 1000 A (1000 V) 60 °C 800 A (1000 V) 70 °C 720 A (690 V) 40 °C 1000 A (690 V) 55 °C 800 A (690 V) 60 °C 800 A (690 V) 70 °C 720 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 6400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1200 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 6800 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 4400 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp)8 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Mechanical Durability5 million
Maximum Mechanical Switching Frequency3600 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 220 ... 230 V 60 Hz 240 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 125 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 140 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 3500 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 4000 V·A
Power Lossat Rated Operating Conditions per Pole 80 W
Operate TimeBetween Coil De-energization and NC Contact Closing 10 ... 20 ms Between Coil De-energization and NO Contact Opening 13 ... 23 ms Between Coil Energization and NC Contact Opening 25 ... 55 ms Between Coil Energization and NO Contact Closing 30 ... 60 ms
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Connecting Terminals (delivered in open position) Main PolesFlat type c/w screws and bolts
Terminal TypeMain Circuit: Bars
Product NameBlock Contactor
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -50 ... 70 °C
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationNo declaration needed
Toxic Substances Control Act - TSCA2CMT2023-006525
CQC CertificateCQC2003010304094983
Declaration of Conformity - CCC2020980304001285
Declaration of Conformity - CE2CMT2015-005442
Package Level 1 Unitsbox 1 piece
Package Level 1 Width317 mm
Package Level 1 Depth / Length373 mm
Package Level 1 Height234 mm
Package Level 1 Gross Weight17.5 kg
Package Level 1 EAN7320500194249
IDEA Granular Category Code (IGCC)4755 >> Contactors

For complete electrical ratings, applicable standards, connection requirements and installation instructions, consult the official ABB reference ↗.